SIMATIC ET 200S – PM-E F PROFIsafe F-Power Module – Siemens Fail-Safe I/O Modules

USD $ 354.41USD $ 397.77

SKU: N/A

Siemens Power Modules SIMATIC ET 200S Product Specifications:

Article number 6ES7138-4CF03-0AB0 6ES7138-4CF42-0AB0
ET200S, Powermod. PM-E F PM, DC24V ET200S, Powermod. PM-E F PP, DC24V
Supply voltage
Load voltage L+
● Rated value (DC) 24 V 24 V
● Reverse polarity protection No No
Input current
From load voltage L+ (no load), typ. 100 mA 100 mA
from backplane bus 24 V DC, max. 28 mA 28 mA
Power loss
Power loss, typ. 4 W 4 W
Address area
Address space per module
● Inputs 5 byte 5 byte
● Outputs 5 byte 5 byte
Digital outputs
Number of digital outputs 2 1; Relays
Short-circuit protection Yes; Electronic No
● Response threshold, typ. Response threshold (short-circuit): 5 to 12 A; response threshold (external short-circuit to ground): 5 to 12 A; response threshold (external short-circuit to P potential): 25 to 45 A
Limitation of inductive shutdown voltage to L+ (-2x 47 V)
Controlling a digital input No Yes
Switching capacity of the outputs
● on lamp load, max. 10 W 100 W
Load resistance range
● lower limit 12 Ω
● upper limit 1 kΩ
Output voltage
● for signal “1”, min. L+ (-2,0 V), current sourcing switch: L+ (-1,5 V), voltage drop on current sinking switch: max. 0.5 V
Output current
● for signal “1” rated value 2 A
● for signal “1” permissible range for 0 to 60 °C, min. 20 mA
● for signal “1” permissible range for 0 to 60 °C, max. 2.4 A
● for signal “0” residual current, max. 0.5 mA
Parallel switching of two outputs
● for uprating No
● for redundant control of a load No
Switching frequency
● with resistive load, max. 30 Hz 2 Hz
● with inductive load, max. 0.1 Hz 0.1 Hz; with inductive load to IEC 60947-5-1, DC-13 / AC-15
● on lamp load, max. 10 Hz 2 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max. 10 A 10 A
— up to 55 °C, max. 7 A 8 A
— up to 60 °C, max. 6 A 7 A
vertical installation
— up to 40 °C, max. 6 A 8 A
Relay outputs
Switching capacity of contacts
— with resistive load, up to 50 °C, max. 10 A 10 A
Cable length
● shielded, max. 200 m
● unshielded, max. 200 m
Interrupts/diagnostics/status information
Diagnostics function Yes Yes
Diagnoses
● Diagnostic information readable Yes Yes
● Wire-break Yes No
● Short-circuit Yes Yes
● missing load voltage Yes Yes
Diagnostics indication LED
● Rated load voltage PWR (green) Yes Yes
● Group error SF (red) Yes Yes
● Status indicator digital output (green) Yes Yes
Potential separation
Potential separation digital outputs
● between the channels No No
● between the channels and backplane bus Yes Yes
● Between the channels and load voltage L+ No No
Isolation
Isolation tested with 500 V DC 500 V DC
Standards, approvals, certificates
Highest safety class achievable in safety mode
● acc. to EN 954 4 4
● Performance level according to ISO 13849-1 e e
● SIL acc. to IEC 61508 Up to SIL 3 With Std-DO: Max. SIL 2, without Std-DO max. SIL 3 depending on configuration
Dimensions
Width 30 mm 30 mm
Height 81 mm 81 mm
Depth 52 mm 52 mm
Weights
Weight, approx. 88 g 80 g
Weight N/A
Dimensions N/A

Related products