Scalable and cost-optimized configuration of a ET 200SP station is achieved by a comprehensive portfolio of digital and analog IO modules.

SIMATIC ET 200SP is about 50% narrower than other distributed peripheries. With its height of 115 millimeters, the system can accommodate 16 channels with single-wire connection (without AUX-plugs). For a 3-wire connection with AUX-plugs the height for 8 channels is 140 millimeters. The depth is 75 millimeters. In order to keep its small size, the power module for load group formation is integrated into the system of SIMATIC ET 200SP.

The peripheral modules are labelled with different colored squares to identify easily the type of module.

Siemens Digital Output Modules ET 200SP Product Specifications:

[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]

Article number 6ES7132-6BF61-0AA0 6ES7132-6BH00-0AA0 6ES7132-6BF01-0AA0 6ES7132-6BH01-0BA0 6ES7132-6BF01-0BA0
ET 200SP, DQ 8x 24VDC/0,5A SINK BA, PU 1 ET 200SP, DQ 16X24VDC/0,5A BA, PU 1 ET 200SP, DQ 8x 24V DC/0,5A Basic, PU 1 ET 200SP, DQ 16x 24V DC/0,5A ST, PU 1 ET 200SP, DQ 8x 24V DC/0,5A ST, PU 1
General information
Product type designation DQ 8x24VDC/0,5A SNK BA DQ 16x24VDC/0.5A BA DQ 8x24VDC/0.5A BA DQ 16x24VDC/0.5A ST DQ 8x24VDC/0.5A ST
HW functional status From FS02 From FS03 From FS02 From FS03 From FS02
Firmware version V0.0 V0.0 V0.0 V0.0 V0.0
● FW update possible No No No No No
usable BaseUnits BU type A0 BU type A0 BU type A0 BU type A0 BU type A0
Color code for module-specific color identification plate CC01 CC00 CC02 CC00 CC02
Product function
● I&M data Yes; I&M0 to I&M3 Yes; I&M0 to I&M3 Yes; I&M0 to I&M3 Yes; I&M0 to I&M3 Yes; I&M0 to I&M3
● Isochronous mode No No No No No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V14 V14 V14 V14 V14
● STEP 7 configurable/integrated from version V5.5 SP3 STEP 7 V5.5 or higher V5.5 SP3 V5.5 SP3 V5.5 SP3 or higher
● PCS 7 configurable/integrated from version V8.1 SP1 V8.1 SP1
● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher One GSD file each, Revision 3 and 5 and higher One GSD file each, Revision 3 and 5 and higher One GSD file each, Revision 3 and 5 and higher One GSD file each, Revision 3 and 5 and higher
● PROFINET from GSD version/GSD revision GSDML V2.3 GSDML V2.3 GSDML V2.3 GSDML V2.3 GSDML V2.3
Operating mode
● DQ Yes Yes Yes Yes Yes
● DQ with energy-saving function No No No No No
● PWM No No No No No
● Oversampling No No No No No
● MSO No No No No No
Redundancy
● Redundancy capability Yes
Supply voltage
Rated value (DC) 24 V 24 V 24 V 24 V 24 V
permissible range, lower limit (DC) 19.2 V 19.2 V 19.2 V 19.2 V 19.2 V
permissible range, upper limit (DC) 28.8 V 28.8 V 28.8 V 28.8 V 28.8 V
Reverse polarity protection Yes Yes Yes Yes
Input current
Current consumption, max. 55 mA; without load 45 mA; without load 60 mA; without load 35 mA; without load
output voltage / header
Rated value (DC) 24 V 24 V 24 V 24 V 24 V
Power loss
Power loss, typ. 1.5 W 1 W 1 W 1 W 1 W
Address area
Address space per module
● Address space per module, max. 1 byte 2 byte; + 2 bytes for QI information 1 byte; + 1 byte for QI information
● Outputs 1 byte 2 byte
Hardware configuration
Automatic encoding Yes Yes Yes Yes Yes
● Mechanical coding element Yes Yes Yes Yes Yes
● Type of mechanical coding element type B Type A Type A Type A Type A
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0 BU type A0 BU type A0 BU type A0
● 2-wire connection BU type A0 + Potential distributor module BU type A0 BU type A0 + Potential distributor module BU type A0
● 3-wire connection BU type A0 + Potential distributor module BU type A0 with AUX terminals or potential distributor module BU type A0 + Potential distributor module BU type A0 with AUX terminals or potential distributor module
● 4-wire connection BU type A0 + Potential distributor module BU type A0 + Potential distributor module BU type A0 + Potential distributor module BU type A0 + Potential distributor module
Digital outputs
Type of digital output Source output (PNP, current-sourcing) Source output (PNP, current-sourcing) Source output (PNP, current-sourcing) Source output (PNP, current-sourcing) Source output (PNP, current-sourcing)
Number of digital outputs 8 16 8 16 8
Current-sinking Yes No No
Current-sourcing Yes Yes Yes Yes
Digital outputs, parameterizable Yes Yes Yes Yes Yes
Short-circuit protection Yes Yes Yes; per channel, electronic Yes Yes
● Response threshold, typ. 1.5 A 1.4 A; 0.7 to 1.9 A 1 A 1 A; 0.7 to 1.3 A 1 A
Open-circuit detection No Yes
Limitation of inductive shutdown voltage to Typ. 47 V Typ. L+ (-53 V) Typ. L+ (-50 V) Typ. L+ (-50 V) Typ. L+ (-50 V)
Controlling a digital input Yes Yes Yes Yes Yes
Switching capacity of the outputs
● with resistive load, max. 0.5 A 0.5 A 0.5 A 0.5 A 0.5 A
● on lamp load, max. 5 W 5 W 5 W 5 W 5 W
Load resistance range
● lower limit 48 Ω 48 Ω 48 Ω 48 Ω 48 Ω
● upper limit 3 400 Ω 100 kΩ 100 kΩ 12 kΩ 12 kΩ
Output voltage
● for signal “1”, min. L+ (-0.8 V)
Output current
● for signal “1” rated value 0.5 A 0.5 A 0.5 A 0.5 A 0.5 A
● for signal “1” permissible range, max. 0.5 A 0.5 A 0.5 A
● for signal “0” residual current, max. 5 µA 30 µA 10 µA 0.1 mA 0.1 mA
Output delay with resistive load
● “0” to “1”, typ. 80 µs; at rated load 50 µs
● “0” to “1”, max. 300 µs 150 µs; at rated load 100 µs; at rated load 50 µs; at rated load
● “1” to “0”, typ. 100 µs; at rated load 100 µs
● “1” to “0”, max. 600 µs 200 µs; at rated load 150 µs; at rated load 100 µs; at rated load
Parallel switching of two outputs
● for uprating No No No No No
● for redundant control of a load Yes Yes Yes Yes Yes
Switching frequency
● with resistive load, max. 100 Hz 100 Hz 100 Hz 100 Hz 100 Hz
● with inductive load, max. 0.5 Hz 2 Hz 2 Hz 2 Hz 2 Hz
● on lamp load, max. 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz
Total current of the outputs
● Current per channel, max. 0.5 A 0.5 A 0.5 A 0.5 A 0.5 A
● Current per module, max. 4 A 8 A 4 A 8 A 4 A
Total current of the outputs (per module)
horizontal installation
— up to 40 °C, max. 8 A
— up to 50 °C, max. 6 A
— up to 60 °C, max. 4 A 8 A 4 A 4 A 4 A
vertical installation
— up to 30 °C, max. 8 A
— up to 40 °C, max. 6 A
— up to 50 °C, max. 4 A 8 A 4 A 4 A 4 A
Cable length
● shielded, max. 1 000 m 1 000 m 1 000 m 1 000 m 1 000 m
● unshielded, max. 600 m 600 m 600 m 600 m 600 m
Interrupts/diagnostics/status information
Diagnostics function Yes Yes Yes Yes Yes
Substitute values connectable Yes Yes Yes Yes Yes
Alarms
● Diagnostic alarm Yes Yes Yes Yes Yes
Diagnoses
● Monitoring the supply voltage Yes Yes Yes Yes Yes
● Wire-break No No No Yes; Module-wise Yes; Module-wise
● Short-circuit No No No
● Short-circuit to M Yes; Module-wise Yes; Module-wise
● Short-circuit to L+ Yes; Module-wise Yes; Module-wise
● Group error Yes Yes Yes Yes Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED Yes; green PWR LED Yes; green PWR LED Yes; green PWR LED Yes; green PWR LED
● Channel status display Yes; green LED Yes; green LED Yes; green LED Yes; green LED Yes; green LED
● for channel diagnostics No No No No No
● for module diagnostics Yes; green/red DIAG LED Yes; green/red DIAG LED Yes; green/red DIAG LED Yes; green/red DIAG LED Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No No No No No
● between the channels and backplane bus Yes Yes Yes Yes Yes
● between the channels and the power supply of the electronics No No
Isolation
Isolation tested with 707 V DC (type test) 707 V DC (type test) 707 V DC (type test) 707 V DC (type test) 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions No No No No No
Suitable for safety-related tripping of standard modules No Yes; see FAQ Entry ID: 39198632 Yes; see FAQ Entry ID: 39198632 Yes; see FAQ Entry ID: 39198632
Highest safety class achievable in safety mode
● Performance level according to ISO 13849-1 PL d PL d PL d
● SIL acc. to IEC 61508 SIL 2 SIL 2 SIL 2
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -25 °C -30 °C -30 °C; < 0 °C as of FS02 -30 °C; < 0 °C as of FS03 -30 °C; < 0 °C as of FS02
● horizontal installation, max. 60 °C 60 °C 60 °C 60 °C 60 °C
● vertical installation, min. -25 °C -30 °C -30 °C; < 0 °C as of FS02 -30 °C; < 0 °C as of FS03 -30 °C; < 0 °C as of FS02
● vertical installation, max. 50 °C 50 °C 50 °C 50 °C 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 15 mm 15 mm 15 mm 15 mm 15 mm
Height 73 mm 73 mm 73 mm 73 mm 73 mm
Depth 58 mm 58 mm 58 mm 58 mm 58 mm
Weights
Weight, approx. 30 g 30 g 30 g 30 g 30 g