Article number 6ES7322-1BH01-0AA0 6ES7322-1BH10-0AA0 6ES7322-1BL00-0AA0 6ES7322-1BP00-0AA0 6ES7322-1BP50-0AA0 6ES7322-8BF00-0AB0
SM322, 16DO 24V DC, 0,5A SM322 High Speed, 16DO 24V DC, 0.5A SM322, 32DO 24V DC, 0,5A SM322 64DA, DC24V, 0,3A P-write SM322 64DO, DC24V, 0.3A M-write SM322, 8DO, 24V DC, 0,5A
Supply voltage
Load voltage L+
● Rated value (DC) 24 V 24 V 24 V 24 V 24 V 24 V
● permissible range, lower limit (DC) 20.4 V 20.4 V 20.4 V 20.4 V 20.4 V 20.4 V
● permissible range, upper limit (DC) 28.8 V 28.8 V 28.8 V 28.8 V 28.8 V 28.8 V
Input current
from load voltage L+ (without load), max. 80 mA 110 mA 160 mA 75 mA 75 mA 90 mA
from backplane bus 5 V DC, max. 80 mA 70 mA 110 mA 100 mA 100 mA 70 mA
Power loss
Power loss, typ. 4.9 W 5 W 6.6 W 6 W 6 W 5 W
Digital outputs
Number of digital outputs 16 16 32 64 64 8
Short-circuit protection Yes; Electronic Yes; Electronic Yes; Electronic Yes; Electronic Yes; Electronic Yes; Electronic
● Response threshold, typ. 1 A 1 A 1 A 0.7 to 1.9 A 0.75 to 1.5 A
Limitation of inductive shutdown voltage to L+ (-53 V) L+ (-53 V) L+ (-53 V) L+ (-53 V) M+ (45 V) L+ (-45 V)
Controlling a digital input Yes Yes Yes Yes Yes Yes
Switching capacity of the outputs
● on lamp load, max. 5 W 5 W 5 W 5 W 5 W 5 W
Load resistance range
● lower limit 48 Ω 48 Ω 48 Ω 80 Ω 80 Ω 48 Ω
● upper limit 4 kΩ 4 kΩ 4 kΩ 10 kΩ 10 kΩ 3 kΩ
Output voltage
● for signal “1”, min. L+ (-0.8 V) L+ (-0.8 V) L+ (-0.8 V) L+ (-0.5 V) M+ (0.5 V) L+ (-0.8 to -1.6 V)
Output current
● for signal “1” rated value 0.5 A 0.5 A 0.5 A 0.3 A 0.3 A 0.5 A
● for signal “1” permissible range, min. 2.4 mA 2.4 mA
● for signal “1” permissible range, max. 0.36 A 0.36 A
● for signal “1” permissible range for 0 to 40 °C, min. 5 mA 5 mA 5 mA 10 mA
● for signal “1” permissible range for 0 to 40 °C, max. 0.6 A 0.6 A 0.6 A 0.6 A
● for signal “1” permissible range for 40 to 60 °C, min. 5 mA 5 mA 5 mA 10 mA
● for signal “1” permissible range for 40 to 60 °C, max. 0.6 A 0.6 A 0.6 A 0.6 A
● for signal “1” minimum load current 5 mA 5 mA 5 mA 10 mA
● for signal “0” residual current, max. 0.5 mA 0.5 mA 0.5 mA 0.1 mA 0.5 mA
Output delay with resistive load
● “0” to “1”, max. 100 µs 100 µs 100 µs 550 µs 450 µs 180 µs
● “1” to “0”, max. 500 µs 200 µs 500 µs 550 µs 450 µs 245 µs
Parallel switching of two outputs
● for uprating No No No No No No
● for redundant control of a load Yes Yes; only outputs of the same group Yes; only outputs of the same group Yes Yes Outputs with series diodes only
Switching frequency
● with resistive load, max. 100 Hz 1 000 Hz 100 Hz 100 Hz 100 Hz 100 Hz
● with inductive load, max. 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz 2 Hz
● with inductive load (acc. to IEC 60947-5-1, DC13), max. 0.5 Hz 0.5 Hz 0.5 Hz 2 Hz
● on lamp load, max. 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz 10 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max. 4 A 4 A 4 A 1.6 A 1.6 A 4 A
— up to 60 °C, max. 3 A 3 A 3 A 1.2 A 1.2 A 3 A
vertical installation
— up to 40 °C, max. 2 A 2 A 2 A 1.6 A 1.6 A 4 A
Cable length
● shielded, max. 1 000 m 1 000 m 1 000 m 1 000 m 1 000 m 1 000 m
● unshielded, max. 600 m 600 m 600 m 600 m 600 m 600 m
Interrupts/diagnostics/status information
Alarms No No No No No
Diagnostics function No No No No No Yes; Parameterizable
Alarms
● Diagnostic alarm No No No No No Yes; Parameterizable
Diagnoses
● Diagnostic information readable No No No Yes
● Wire-break No No No No No Yes
● Short-circuit No No No No No Yes
● Fuse blown No No No No No
● missing load voltage No No No No No Yes
Diagnostics indication LED
● Rated load voltage PWR (green) No No No No No
● Fuse OK FSG (green) No No No No No
● Group error SF (red) No No Yes
● Status indicator digital output (green) Yes Yes; per channel Yes; per channel Yes Yes; per channel
● Channel fault indicator F (red) No No Yes
Potential separation
Potential separation digital outputs
● between the channels Yes Yes Yes No No
● between the channels, in groups of 8 8 8 16 16 8
● between the channels and backplane bus Yes; Optocoupler Yes; Optocoupler Yes; Optocoupler Yes; Optocoupler Yes; Optocoupler Yes; Optocoupler
Isolation
Isolation tested with 500 V DC 500 V DC 500 V DC 500 V DC 500 V DC 500 V DC
connection method / header
required front connector 20-pin 20-pin 40-pin Cable: 6ES7392-4Bxx0-0AA0 terminal blocks: 6ES7392-1xN00-0AA0 Cable: 6ES7392-4Bxx0-0AA0 terminal blocks: 6ES7392-1xN00-0AA0 20-pin
Dimensions
Width 40 mm 40 mm 40 mm 40 mm 40 mm 40 mm
Height 125 mm 125 mm 125 mm 125 mm 125 mm 125 mm
Depth 120 mm 120 mm 120 mm 112 mm 112 mm 120 mm
Weights
Weight, approx. 190 g 200 g 260 g 230 g 230 g 210 g

 

Article number 6ES7322-5GH00-0AB0 6ES7322-1CF00-0AA0 6ES7322-1BF01-0AA0 6ES7322-1FF01-0AA0 6ES7322-5FF00-0AB0 6ES7322-1FH00-0AA0
SM322, 16DO, AC/DC24-48V, 0,5A SM322, 8DO, 48-125V DC, 1,5A SM322, 8DO, 24V DC, 2A SM322, 8DO, 120/230V AC, 1A SM322, 8DO, AC120/230V, 2A SM322, 16DO, 120/230V AC, 1A
Supply voltage
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Load voltage L+
● Rated value (DC) 24 V; 24 / 48 48 V; 48 V DC to 125 V DC 24 V
● permissible range, lower limit (DC) 20.4 V 40 V 20.4 V
● permissible range, upper limit (DC) 57.6 V 140 V 28.8 V
● Reverse polarity protection Yes Yes; through fuse
Load voltage L1
● Rated value (AC) 230 V; 120/230 V AC 230 V; 120/230 V AC 230 V; 120/230 V AC
● permissible range, lower limit (AC) 93 V 79 V 79 V
● permissible range, upper limit (AC) 264 V 264 V 264 V
● permissible frequency range, lower limit 47 Hz
● permissible frequency range, upper limit 63 Hz
Input current
from supply voltage L+, max. 200 mA
from load voltage L+ (without load), max. 2 mA 60 mA
from load voltage L1 (without load), max. 2 mA 2 mA 2 mA
from backplane bus 5 V DC, max. 100 mA 100 mA 40 mA 100 mA 100 mA 200 mA
Power loss
Power loss, typ. 2.8 W 7.2 W 6.8 W 8.6 W 8.6 W 8.6 W
Digital outputs
Number of digital outputs 16 8 8 8 8 16
Short-circuit protection No; to be provided externally Yes; Electronic Yes; Electronic Yes; Fuse 8 A, 250 V; per group Yes; to be provided externally; fuse 3.15 A / 250 V, quick response Yes; Fuse 8 A, 250 V; per group
● Response threshold, typ. 4.4 A 3 A
● required current for fuse shutdown, min. 40 A 40 A
● Response time, max. 300 ms 300 ms
Limitation of inductive shutdown voltage to M (-1 V) L+ (-48 V)
Controlling a digital input Yes Yes Yes Yes Yes Yes
Size of motor starters according to NEMA, max. Size 5 according to NEMA 5 NEMA compliant Size 5 according to NEMA 4 NEMA compliant
Spare fuses 6.3 A / 250 V, quick-response, 5x 20 mm 8 A / quick response 8 A / quick response
Zero-crossing switch Yes; Max. 60 V Yes; 60 V
Switching capacity of the outputs
● on lamp load, max. 2.5 W 15 W; 15 W (48 V) or 40 W (125 V) 10 W 50 W 50 W 50 W
Load resistance range
● lower limit 12 Ω
● upper limit 4 kΩ
Output voltage
● for signal “1”, min. L+ (-0.25 V) L+ (-1.2 V) L+ (-0.8 V) L1 (-1.5 V) L1 (-8.5 V)
● for signal “1” (at max. current), min. L1 (-1.5 V) L1 (-1.5 V)
● for signal “1” (at min. current), min. L1 (-8.5 V) L1 (-8.5 V)
Output current
● for signal “1” rated value 0.5 A 1.5 A 2 A 2 A 2 A 1 A
● for signal “1” permissible range for 0 to 40 °C, min. 10 mA 5 mA 10 mA 10 mA 10 mA
● for signal “1” permissible range for 0 to 40 °C, max. 0.5 A 1.5 A 2.4 A 2 A 2 A 1 A
● for signal “1” permissible range for 40 to 60 °C, min. 10 mA 5 mA 10 mA 10 mA 10 mA
● for signal “1” permissible range for 40 to 60 °C, max. 0.5 A 1.5 A 2.4 A 1 A 1 A 0.5 A
● for signal “1” minimum load current 10 mA 5 mA 10 mA 10 mA 10 mA
● for signal “1” permissible surge current, max. 1.5 A; for 50 ms, 1 A 2 s one-time 3 A; for 10 ms 20 A; max. 1 AC cycle 20 A; with 2 half waves 20 A; with 2 half waves
● for signal “0” residual current, max. 10 µA 0.5 mA 0.5 mA 2 mA 2 mA 2 mA
Output delay with resistive load
● “0” to “1”, max. 6 ms 2 ms 100 µs 1 AC cycle
● “1” to “0”, max. 3 ms 15 ms 500 µs 1 AC cycle
Parallel switching of two outputs
● for uprating No No No No No No
● for redundant control of a load Yes Yes; only outputs of the same group Yes Yes Yes Yes; only outputs of the same group
Switching frequency
● with resistive load, max. 10 Hz 25 Hz 100 Hz 10 Hz 10 Hz 10 Hz
● with inductive load, max. 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz
● with inductive load (acc. to IEC 60947-5-1, DC13), max. 0.5 Hz 0.5 Hz 0.5 Hz
● with inductive load (acc. to IEC 60947-5-1, AC15), max. 0.5 Hz 0.5 Hz 0.5 Hz
● on lamp load, max. 0.5 Hz 10 Hz 10 Hz 1 Hz 1 Hz 1 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max. 0.5 A; 8 A per module 6 A 4 A 4 A 8 A 4 A
— up to 50 °C, max. 4 A
— up to 60 °C, max. 0.5 A; 8 A per module 3 A 4 A 2 A 4 A 2 A
vertical installation
— up to 40 °C, max. 0.5 A; 8 A per module 4 A 4 A 2 A 4 A 2 A
Cable length
● shielded, max. 1 000 m 1 000 m 1 000 m 1 000 m 1 000 m 1 000 m
● unshielded, max. 600 m 600 m 600 m 600 m 600 m 600 m
Interrupts/diagnostics/status information
Alarms No No No
Diagnostics function Yes; Parameterizable No No Yes; Fuse blown or load voltage missing Yes; Parameterizable Yes; Fuse blown or load voltage missing
Alarms
● Diagnostic alarm Yes; Parameterizable No No No Yes; Parameterizable No
Diagnoses
● Diagnostic information readable Yes
● Wire-break No No No No
● Short-circuit No No No No
● Fuse blown No No Yes Yes
● missing load voltage No No Yes No
Diagnostics indication LED
● Rated load voltage PWR (green) No No Yes No
● Fuse OK FSG (green) No No Yes Yes; Red LED for fuse
● Group error SF (red) Yes Yes Yes Yes Yes
● Status indicator digital output (green) Yes Yes Yes; per channel Yes Yes Yes
Potential separation
Potential separation digital outputs
● between the channels Yes Yes Yes Yes Yes
● between the channels, in groups of 1 4 4 4 1 8
● between the channels and backplane bus Yes; Optocoupler Yes; Optocoupler Yes; Optocoupler Yes; Optocoupler Yes; Optocoupler Yes; Optocoupler
● between the channels and the power supply of the electronics Yes
Isolation
Isolation tested with 1 500 V AC 1 500 V AC 500 V DC 1 500 V AC 1 500 V AC 4 000 V DC
connection method / header
required front connector 40-pin 20-pin 20-pin 20-pin 40-pin 20-pin
Dimensions
Width 40 mm 40 mm 40 mm 40 mm 40 mm 40 mm
Height 125 mm 125 mm 125 mm 125 mm 125 mm 125 mm
Depth 120 mm 120 mm 120 mm 120 mm 120 mm 120 mm
Weights
Weight, approx. 260 g 250 g 190 g 275 g 275 g 275 g

 

Article number 6ES7322-1FL00-0AA0 6ES7322-1HF01-0AA0 6ES7322-1HF10-0AA0 6ES7322-5HF00-0AB0 6ES7322-1HH01-0AA0
SM322, 32DO, 120/230V AC, 1A SM322, 8DA, 24V DC/2A or 230V AC/2A SM322, 8DA, 24V DC/5A OR 230V AC/5A SM322, 8DO Relay, 24VDC, 120-230V AC, 5A SM322, 16DO Relay
Supply voltage
Load voltage L+
● Rated value (DC) 24 V 120 V 24 V 120 V
● permissible range, lower limit (DC) 24 V
● permissible range, upper limit (DC) 120 V
Load voltage L1
● Rated value (AC) 120 V; 120/230 V AC 230 V 230 V 230 V
● permissible range, lower limit (AC) 79 V
● permissible range, upper limit (AC) 264 V
● permissible frequency range, lower limit 47 Hz
● permissible frequency range, upper limit 63 Hz
Input current
from supply voltage L+, max. 160 mA 125 mA 160 mA 250 mA
from load voltage L1 (without load), max. 10 mA
from backplane bus 5 V DC, max. 190 mA 40 mA 40 mA 100 mA 100 mA
Power loss
Power loss, typ. 25 W 3.2 W 3.2 W 3.5 W 4.5 W
Digital outputs
Number of digital outputs 32 8; Relays 8; Relays 8; Relays 16; Relays
Short-circuit protection No No No; to be provided externally No; to be provided externally No
Controlling a digital input Yes Yes Yes Yes Yes
Size of motor starters according to NEMA, max. Size 4 according to NEMA Size 5 according to NEMA
Zero-crossing switch Yes; Max. 60 V
Switching capacity of the outputs
● on lamp load, max. 50 W 50 W 1 500 W; 230 V AC 1 500 W; 230 V AC 50 W; 230 V AC
● Low energy/fluorescent lamps with electronic control gear 10x 58 W 10x 58 W 10x 58 W
● Fluorescent tubes, conventionally compensated 1x 58 W 1x 58 W 1x 58 W
● Fluorescent tubes, uncompensated 10x 58 W 10x 58 W 10x 58 W
Output voltage
● for signal “1”, min. L1 (-0.8 V)
Output current
● for signal “1” rated value 1 A 2 A 5 A 5 A 2 A
● for signal “1” permissible range for 0 to 40 °C, min. 10 mA
● for signal “1” permissible range for 0 to 40 °C, max. 1 A
● for signal “1” permissible range for 40 to 60 °C, min. 10 mA
● for signal “1” permissible range for 40 to 60 °C, max. 1 A
● for signal “1” minimum load current 10 mA 5 mA 5 mA 10 mA 10 mA
● for signal “1” permissible surge current, max. 10 A; per group (for 2 AC cycles)
● for signal “0” residual current, max. 2 mA
Output delay with resistive load
● “0” to “1”, max. 1 AC cycle
● “1” to “0”, max. 1 AC cycle
Parallel switching of two outputs
● for uprating No No No No No
● for redundant control of a load Yes; only outputs of the same group Yes Yes Yes Yes
Switching frequency
● with resistive load, max. 10 Hz 2 Hz 2 Hz 2 Hz 1 Hz
● with inductive load, max. 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz
● with inductive load (acc. to IEC 60947-5-1, AC15), max. 0.5 Hz
● With inductive load (to IEC 60947-5-1, DC13/AC15), max. 0.5 Hz 0.5 Hz 0.5 Hz 0.5 Hz
● on lamp load, max. 1 Hz 2 Hz 2 Hz 2 Hz 1 Hz
● mechanical, max. 10 Hz 10 Hz 10 Hz 10 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max. 4 A
— up to 60 °C, max. 3 A 5 A 5 A 8 A
vertical installation
— up to 40 °C, max. 4 A 5 A 5 A 8 A
Relay outputs
● Rated supply voltage of relay coil L+ (DC) 24 V; 110 mA 24 V 24 V
● Contact connection (internal) Yes; SIOV-CU4032 K275G No Yes; 330 Ohm, 0.1uF No
● Number of operating cycles, max. 300 000; 230 V AC: 100 000; 120 V AC: 200 000; 24 V DC: 300 000 (at 2 A) 300 000; 300 000 (24 V DC, at 2 A); 200 000 (120 V AC, at 3 A); 100 000 (230 V AC, at 3 A) 100 000; 100 000 (24 V DC, at 5 A), 100 000 (230 V AC, at 5 A) 100 000; 50 000 (24 V DC, at 2 A); 700 000 (120 V AC, at 2 A); 100 000 (230 V AC, at 2 A)
Switching capacity of contacts
— with inductive load, max. 2 A; 2 A (230 V AC), 2 A (24 V DC) 3 A; 3 A (230 V DC), 2 A (24 V AC) 5 A; 5 A (230 V DC), 5 A (24 V AC) 2 A; 2 A (230 V AC), 2 A (24 V DC)
— with resistive load, max. 2 A 8 A; 8 A (230 V DC), 5 A (24 V AC) 5 A; 5 A (230 V DC), 5 A (24 V AC) 2 A; 2 A (230 V AC), 2 A (24 V DC)
— Thermal continuous current, max. 3 A 8 A 5 A 2 A
Cable length
● shielded, max. 1 000 m 1 000 m 1 000 m 1 000 m 1 000 m
● unshielded, max. 600 m 600 m 600 m 600 m 600 m
Interrupts/diagnostics/status information
Alarms No No No Yes No
Diagnostics function Yes; Fuse blown or load voltage missing No No Yes; Parameterizable No
Alarms
● Diagnostic alarm No No No Yes; Parameterizable No
Diagnoses
● Diagnostic information readable Yes
● Wire-break No No No
● Short-circuit No No No
● Fuse blown No No No
● missing load voltage No No No
Diagnostics indication LED
● Rated load voltage PWR (green) No No No
● Fuse OK FSG (green) No No No
● Group error SF (red) Yes Yes
● Status indicator digital output (green) Yes; per channel Yes Yes Yes Yes
Potential separation
Potential separation digital outputs
● between the channels Yes Yes Yes Yes Yes
● between the channels, in groups of 8 2 1 1 8
● between the channels and backplane bus Yes; Optocoupler Yes; Optocoupler Yes; Optocoupler Yes; Optocoupler Yes; Optocoupler
● Between the channels and the power supply of the relays Yes
Isolation
Isolation tested with 4 000 V DC 1 500 V AC 2 000 V AC 1 500 V AC 1 500 V AC
connection method / header
required front connector 20-pin 20-pin 40-pin 40-pin 20-pin
Dimensions
Width 80 mm 40 mm 40 mm 40 mm 40 mm
Height 125 mm 125 mm 125 mm 125 mm 125 mm
Depth 117 mm 120 mm 120 mm 120 mm 120 mm
Weights
Weight, approx. 500 g 190 g 320 g 320 g 250 g
Weight N/A
Dimensions N/A