S8FS-C – S8FS-C0150[][] – Omron Switch Mode Power Supply

USD $ 27.50USD $ 39.16

SKU: N/A
Power
rating
Input voltage Output
voltage
(VDC)
Output
current
Built-
in fan
Model with
terminal block
facing upward
150 W 100 to 120 VAC,
200 to 240 VAC
(allowable range:
90 to 132 VAC,
180 to 264 VAC, or
254 to 373 VDC
(Select with the
switch.) *2)
5 V 26 A None S8FS-C15005
12 V 12.5 A S8FS-C15012
15 V 10 A S8FS-C15015
24 V 6.5 A S8FS-C15024
36 V 4.3 A S8FS-C15036
48 V 3.3 A S8FS-C15048

 

Note: You can use brackets that are sold separately to mount the Power Supplies to DIN Rail. Refer to Mounting Brackets
(Order Separately) on Data Sheet.
*1. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC.
*2. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 120 VAC, 200 to 240 VAC.

 

Ratings, Characteristics, and Functions

Power rating 150 W
Output voltage (VDC) 5 V 12 V 15 V 24 V 36 V 48 V
Efficiency * 115 VAC input 81% typ. 84% typ. 85% typ. 86% typ. 86% typ. 87% typ.
230 VAC input 82% typ. 85% typ. 86% typ. 87% typ. 87% typ. 88% typ.
Input Voltage range * Single phase 90 to 132 VAC , Single phase 180 to 264 VAC , 254 to 373
VDC Select with the switch. (The L terminal for the DC input is the
positive side and safety standards do not apply.) (Derating is required
according to the input voltage. Refer to Derating Curves on Data Sheet.)
Frequency * 50 /60 Hz (47 to 450 Hz)
Current * 115 VAC input 2.8 A typ.
230 VAC input 1.6 A typ.
Power factor
Leakage
current
115 VAC input 0.50 mA 0.50 mA 0.50 mA 0.50 mA 0.40 mA 0.50 mA
230 VAC input 0.75 mA 0.75 mA 0.75 mA 0.70 mA 0.60 mA 0.70 mA
Inrush
current *
(for a cold
start at 25°)
115 VAC input 32 A typ.
230 VAC input 32 A typ.
Output Rated Output Current 26 A 12.5 A 10 A 6.5 A 4.3 A 3.3 A
Voltage adjustment range * -10% to 10% (with V. ADJ)
Ripple & Noise
voltage *
100 to 120
VAC/200 to
240 VAC input
50 mVp-p
max.
90 mVp-p
max.
110 mVp-p
max.
100 mVp-p
max.
200 mVp-p
max.
120 mVp-p
max.
Input variation influence * 0.5% max.
Load variation influence * 1.0% max.
Temperature
variation
influence
100 to 120
VAC/200 to
240 VAC input
0.03%/°C max.
Startup
time *
115 VAC input 770 ms typ. 730 ms typ. 740 ms typ. 770 ms typ. 730 ms typ. 760 ms typ.
230 VAC input 750 ms typ. 720 ms typ. 730 ms typ. 760 ms typ. 720 ms typ. 750 ms typ.
Hold time * 115 VAC input 29 ms typ. 24 ms typ. 27 ms typ. 23 ms typ. 23 ms typ. 21 ms typ.
230 VAC input 35 ms typ. 30 ms typ. 31 ms typ. 28 ms typ. 29 ms typ. 27 ms typ.
Addi-
tional
func-
tions
Overload protection Yes, automatic reset
Overvoltage protection * Yes, 115% or higher of rated output voltage, power shut off (shut off the
input voltage and turn on the input again)
Overheat protection No
Series operation Yes (For up to 2 Power Supplies, external diodes are required.)
Parallel operation No (However, backup operation is possible, external diodes are required.)
Remote sensing No
Remote control No
Output indicator Yes (LED: Green)
Insula-
tion
Withstand voltage 3 kVAC for 1 min. (between all input terminals and output terminals)
current cutoff 20 mA
2 kVAC for 1 min. (between all input terminals and PE terminals) current
cutoff 20 mA
1 kVAC for 1 min. (between all output terminals and PE terminals) current
cutoff 20 mA
Insulation resistance 100 MΩ min. (between all output terminals and all input terminals/PE
terminals) at 500 VDC
Envi-
ron-
ment
Ambient operating temperature -20 to 60°C (Derating is required according to the temperature. Refer
to Derating Curves on Data Sheet.) (with no condensation or icing)
Storage temperature -40 to 85°C (with no condensation or icing)
Ambient operating humidity 20% to 90% (Storage humidity: 10% to 95%)
Vibration resistance 10 to 55 Hz, 0.375-mm half amplitude for 2 h each in X, Y, and Z
directions
10 to 500 Hz, 0.26-mm half amplitude for 1 h each in X, Y, and Z
directions
Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Relia-
bility
MTBF 135,000 hrs min.
Life expectancy * 10 years min.
Con-
struc-
tion
Dimensions (W × H × D) Refer to Dimensions.
Weight 500 g max.
Cooling fan No
Degree of protection
Stan-
dards
Harmonic current emissions Conforms to EN 61000-3-2, GB17625.1
EMI Conducted
Emissions
Conforms to EN 61204-3 Class B, EN 55011 Class B, GB9254
Radiated
Emissions
Conforms to EN 61204-3 Class B, EN 55011 Class B, GB9254
EMS Conforms to EN 61204-3 high severity levels
Safety Standards Approved Standards
UL: cURus UL 62368-1 (Recognition) OVC II Pol2
CSA: cURus C22.2 No62368-1
CCC: GB4943
Conformed Standards
EN: EN 62368-1 OVC II Pol2
RCM (EN61000-6-4)
Marine Standards No
SEMI No
Weight N/A
Model

,

Model

S8FS-C15005, S8FS-C15012

Related products