The CPU 412-5H can be used for the SIMATIC S7-400H and S7-400F/FH. It enables the establishment of an S7-400H high-availability system. It can also be used for the S7-400F/FH fail-safe automation system in conjunction with the F runtime license.
The integrated PROFIBUS DP interfaces enable direct connection as master to the PROFIBUS DP fieldbus.
The integrated PROFINET interface with switch functionality forms the basis for providing 2 externally accessible PROFINET ports. In this way, linear or ring structures can be implemented.
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Article number | 6ES7412-5HK06-0AB0 |
CPU412-5H PN/DP, 1MB F. S7-400H/F/FH | |
General information | |
Product type designation | CPU 412-5H PN/DP |
HW functional status | 1 |
Firmware version | V6.0 |
Product function | |
● Isochronous mode | No |
Engineering with | |
● Programming package | As of STEP 7 V5.5 SP2 with HF1 |
CiR – Configuration in RUN | |
CiR synchronization time, basic load | 100 ms |
CiR synchronization time, time per I/O byte | 0 µs |
Supply voltage | |
Rated value (DC) | Power supply via system power supply |
Input current | |
from backplane bus 5 V DC, typ. | 1.6 A |
from backplane bus 5 V DC, max. | 1.9 A |
from backplane bus 24 V DC, max. | 150 mA; 150 mA per DP interface |
from interface 5 V DC, max. | 90 mA; At each DP interface |
Power loss | |
Power loss, typ. | 7.5 W |
Memory | |
Type of memory | RAM |
Work memory | |
● integrated | 1 Mbyte |
● integrated (for program) | 512 kbyte |
● integrated (for data) | 512 kbyte |
● expandable | No |
Load memory | |
● expandable FEPROM | Yes; with Memory Card (FLASH) |
● expandable FEPROM, max. | 64 Mbyte |
● integrated RAM, max. | 512 kbyte |
● expandable RAM | Yes |
● expandable RAM, max. | 64 Mbyte |
Backup | |
● present | Yes |
● with battery | Yes; all data |
● without battery | No |
Battery | |
Backup battery | |
● Backup current, typ. | 180 µA; Valid up to 40°C |
● Backup current, max. | 1 000 µA |
● Backup time, max. | Dealt with in the module data manual with the secondary conditions and the factors of influence |
● Feeding of external backup voltage to CPU | 5 V DC to 15 V DC |
CPU processing times | |
for bit operations, typ. | 31.25 ns |
for word operations, typ. | 31.25 ns |
for fixed point arithmetic, typ. | 31.25 ns |
for floating point arithmetic, typ. | 62.5 ns |
CPU-blocks | |
DB | |
● Number, max. | 6 000; Number range: 1 to 16000 |
● Size, max. | 64 kbyte |
FB | |
● Number, max. | 3 000; Number range: 0 to 7999 |
● Size, max. | 64 kbyte |
FC | |
● Number, max. | 3 000; Number range: 0 to 7999 |
● Size, max. | 64 kbyte |
OB | |
● Number, max. | see instruction list |
● Size, max. | 64 kbyte |
● Number of free cycle OBs | 1; OB 1 |
● Number of time alarm OBs | 4; OB 10-13 |
● Number of delay alarm OBs | 4; OB 20-23 |
● Number of cyclic interrupt OBs | 4; OB 32-35 |
● Number of process alarm OBs | 4; OB 40-43 |
● Number of DPV1 alarm OBs | 3; OB 55-57 |
● Number of startup OBs | 2; OB 100, 102 |
● Number of asynchronous error OBs | 9; OB 80-88 |
● Number of synchronous error OBs | 2; OB 121, 122 |
Nesting depth | |
● per priority class | 24 |
● additional within an error OB | 1 |
Counters, timers and their retentivity | |
S7 counter | |
● Number | 2 048 |
Retentivity | |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 2 047 |
— preset | Z 0 to Z 7 |
Counting range | |
— lower limit | 0 |
— upper limit | 999 |
IEC counter | |
● present | Yes |
● Type | SFB |
● Number | Unlimited (limited only by RAM capacity) |
S7 times | |
● Number | 2 048 |
Retentivity | |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 2 047 |
— preset | No times retentive |
Time range | |
— lower limit | 10 ms |
— upper limit | 9 990 s |
IEC timer | |
● present | Yes |
● Type | SFB |
● Number | Unlimited (limited only by RAM capacity) |
Data areas and their retentivity | |
Retentive data area (incl. timers, counters, flags), max. | Total working and load memory (with backup battery) |
Flag | |
● Size, max. | 8 192 byte |
● Retentivity available | Yes |
● Retentivity preset | MB 0 to MB 15 |
● Number of clock memories | 8; in 1 memory byte |
Local data | |
● adjustable, max. | 16 kbyte |
● preset | 8 kbyte |
Address area | |
I/O address area | |
● Inputs | 8 kbyte |
● Outputs | 8 kbyte |
Process image | |
● Inputs, adjustable | 8 kbyte |
● Outputs, adjustable | 8 kbyte |
● Inputs, default | 256 byte |
● Outputs, default | 256 byte |
● consistent data, max. | 244 byte |
● Access to consistent data in process image | Yes |
Subprocess images | |
● Number of subprocess images, max. | 15 |
Digital channels | |
● Inputs | 65 536 |
— of which central | 65 536 |
● Outputs | 65 536 |
— of which central | 65 536 |
Analog channels | |
● Inputs | 4 096 |
— of which central | 4 096 |
● Outputs | 4 096 |
— of which central | 4 096 |
Hardware configuration | |
Number of expansion units, max. | 21 |
connectable OPs | 47 |
Multicomputing | No |
Interface modules | |
● Number of connectable IMs (total), max. | 6 |
● Number of connectable IM 460s, max. | 6 |
● Number of connectable IM 463s, max. | 4; Single mode only |
Number of DP masters | |
● integrated | 2 |
● via CP | 10; CP 443-5 Extended |
● Mixed mode IM + CP permitted | No |
● via interface module | 0 |
Number of IO Controllers | |
● integrated | 1 |
● via CP | 0 |
Number of operable FMs and CPs (recommended) | |
● FM | See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections |
● CP, PtP | See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections |
● PROFIBUS and Ethernet CPs | 14; Of which max. 10 CP as DP master |
Slots | |
● required slots | 2 |
Time of day | |
Clock | |
● Hardware clock (real-time) | Yes |
● retentive and synchronizable | Yes |
● Resolution | 1 ms |
● Deviation per day (buffered), max. | 1.7 s; Power off |
● Deviation per day (unbuffered), max. | 8.6 s; Power on |
Operating hours counter | |
● Number | 16 |
● Number/Number range | 0 to 15 |
● Range of values | SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 – 1 hours |
● Granularity | 1 h |
● retentive | Yes |
Clock synchronization | |
● supported | Yes |
● to MPI, master | Yes |
● to MPI, slave | Yes |
● to DP, master | Yes |
● to DP, slave | Yes |
● in AS, master | Yes |
● in AS, slave | Yes |
● on Ethernet via NTP | Yes; As client |
Time difference in system when synchronizing via | |
● Ethernet, max. | 10 ms; Via NTP |
● MPI, max. | 200 ms |
Interfaces | |
Number of RS 485 interfaces | 2 |
Number of other interfaces | 2; Fiber-optic interface |
Optical interface | No |
1. Interface | |
Interface type | MPI/PROFIBUS DP |
Isolated | Yes |
Interface types | |
● RS 485 | Yes |
● Output current of the interface, max. | 150 mA |
Protocols | |
● MPI | Yes |
● PROFIBUS DP master | Yes |
● PROFIBUS DP slave | No |
MPI | |
● Number of connections | 32; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 |
● Transmission rate, max. | 12 Mbit/s |
Services | |
— PG/OP communication | Yes |
— Routing | Yes |
— Global data communication | No |
— S7 basic communication | No |
— S7 communication | Yes |
— S7 communication, as client | Yes |
— S7 communication, as server | Yes |
PROFIBUS DP master | |
● Number of connections, max. | 16; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 |
● Transmission rate, max. | 12 Mbit/s |
● Number of DP slaves, max. | 32 |
Services | |
— PG/OP communication | Yes |
— Routing | Yes |
— Global data communication | No |
— S7 basic communication | No |
— S7 communication | Yes |
— S7 communication, as client | Yes |
— S7 communication, as server | Yes |
— Equidistance | No |
— Isochronous mode | No |
— SYNC/FREEZE | No |
— Activation/deactivation of DP slaves | No |
— Direct data exchange (slave-to-slave communication) | No |
— DPV1 | Yes |
Address area | |
— Inputs, max. | 2 kbyte |
— Outputs, max. | 2 kbyte |
User data per DP slave | |
— User data per DP slave, max. | 244 byte |
— Inputs, max. | 244 byte |
— Outputs, max. | 244 byte |
— Slots, max. | 244 |
— per slot, max. | 128 byte |
PROFIBUS DP slave | |
● Number of connections | No configuration of CPU as DP slave |
2. Interface | |
Interface type | PROFINET |
Isolated | Yes |
automatic detection of transmission rate | Yes; Autosensing |
Autonegotiation | Yes |
Autocrossing | Yes |
Change of IP address at runtime, supported | No |
Number of connection resources | 48 |
Interface types | |
● RJ 45 (Ethernet) | Yes |
● Number of ports | 2 |
● integrated switch | Yes |
Protocols | |
● PROFINET IO Controller | Yes |
● PROFINET IO Device | No |
● PROFINET CBA | No |
● PROFIBUS DP master | No |
● PROFIBUS DP slave | No |
● Open IE communication | Yes |
● Web server | No |
● Point-to-point connection | No |
● Media redundancy | Yes |
PROFINET IO Controller | |
● Transmission rate, max. | 100 Mbit/s |
Services | |
— PG/OP communication | Yes |
— S7 communication | Yes |
— Isochronous mode | No |
— Shared device | Yes; Single mode only |
— Prioritized startup | No |
— Number of connectable IO Devices, max. | 256; In redundant mode via both interfaces |
— Number of connectable IO Devices for RT, max. | 256 |
— of which in line, max. | 256 |
— Activation/deactivation of IO Devices | No |
— IO Devices changing during operation (partner ports), supported | No |
— Device replacement without swap medium | Yes |
— Send cycles | 250 µs, 500 µs, 1 ms, 2 ms, 4 ms |
— Updating time | 250 µs to 512 ms, minimum value depends on the number of configured user data and the configured single or redundant mode |
Address area | |
— Inputs, max. | 8 kbyte |
— Outputs, max. | 8 kbyte |
— User data consistency, max. | 1 024 byte |
Open IE communication | |
● Number of connections, max. | 46 |
● Local port numbers used at the system end | 0, 20, 21, 25, 102, 135, 161, 34962, 34963, 34964, 65532, 65533, 65534, 65535 |
● Keep-alive function, supported | Yes |
3. Interface | |
Interface type | PROFIBUS DP |
Number of connection resources | 16 |
Interface types | |
● RS 485 | Yes |
● Output current of the interface, max. | 150 mA |
Protocols | |
● PROFIBUS DP master | Yes |
● PROFIBUS DP slave | No |
PROFIBUS DP master | |
● Number of connections, max. | 16 |
● Transmission rate, max. | 12 Mbit/s |
● Number of DP slaves, max. | 64 |
Services | |
— PG/OP communication | Yes |
— Routing | Yes |
— Global data communication | No |
— S7 basic communication | No |
— S7 communication | Yes |
— S7 communication, as client | Yes |
— S7 communication, as server | Yes |
— Equidistance | No |
— Isochronous mode | No |
— SYNC/FREEZE | No |
— Activation/deactivation of DP slaves | No |
— Direct data exchange (slave-to-slave communication) | No |
— DPV0 | Yes |
— DPV1 | Yes |
Address area | |
— Inputs, max. | 4 kbyte |
— Outputs, max. | 4 kbyte |
User data per DP slave | |
— User data per DP slave, max. | 244 byte |
— Inputs, max. | 244 byte |
— Outputs, max. | 244 byte |
— Slots, max. | 244 |
— per slot, max. | 128 byte |
4. Interface | |
Interface type | Pluggable synchronization submodule (FO) |
Plug-in interface modules | Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0 |
5. Interface | |
Interface type | Pluggable synchronization submodule (FO) |
Plug-in interface modules | Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0 |
Protocols | |
Redundancy mode | |
Media redundancy | |
— Switchover time on line break, typ. | 200 ms |
— Number of stations in the ring, max. | 50 |
SIMATIC communication | |
● S7 routing | Yes |
Open IE communication | |
● TCP/IP | Yes; via integrated PROFINET interface and loadable FBs |
— Number of connections, max. | 46 |
— Data length, max. | 32 kbyte |
— several passive connections per port, supported | Yes |
● ISO-on-TCP (RFC1006) | Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs |
— Number of connections, max. | 46 |
— Data length, max. | 32 kbyte; 1 452 bytes via CP 443-1 Adv. |
● UDP | Yes; via integrated PROFINET interface and loadable FBs |
— Number of connections, max. | 46 |
— Data length, max. | 1 472 byte |
Web server | |
● supported | No |
Isochronous mode | |
Equidistance | No |
communication functions / header | |
PG/OP communication | Yes |
● Number of connectable OPs without message processing | 47 |
● Number of connectable OPs with message processing | 47; When using Alarm_S/SQ and Alarm_D/DQ |
Data record routing | Yes |
Global data communication | |
● supported | No |
S7 basic communication | |
● supported | No |
S7 communication | |
● supported | Yes |
● as server | Yes |
● as client | Yes |
● User data per job, max. | 64 kbyte |
● User data per job (of which consistent), max. | 462 byte; 1 variable |
S5 compatible communication | |
● supported | Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV) |
● User data per job, max. | 8 kbyte |
● User data per job (of which consistent), max. | 240 byte |
● Number of simultaneous AG-SEND/AG-RECV orders per CPU, max. | 64/64 |
Standard communication (FMS) | |
● supported | Yes; Via CP and loadable FB |
Number of connections | |
● overall | 48 |
● usable for PG communication | |
— reserved for PG communication | 1 |
— adjustable for PG communication, max. | 0 |
● usable for OP communication | |
— reserved for OP communication | 1 |
— adjustable for OP communication, max. | 0 |
● usable for S7 basic communication | |
— reserved for S7 basic communication | 0 |
— adjustable for S7 basic communication, max. | 0 |
● usable for S7 communication | |
— reserved for S7 communication | 0 |
— adjustable for S7 communication, max. | 0 |
● usable for routing | |
— reserved for routing | 0 |
— adjustable for routing, max. | 0 |
S7 message functions | |
Number of login stations for message functions, max. | 47; Max. 47 with Alarm_S/SQ and Alarm_D/DQ (OPs); max. 8 with Alarm, Alarm_8, Alarm_8P, Notify and Notify_8 (e.g. WinCC) |
Symbol-related messages | No |
SCAN procedure | No |
Program alarms | Yes |
Process diagnostic messages | Yes |
simultaneously active Alarm-S blocks, max. | 250; Simultaneously active alarm_S/SQ blocks or alarm_D/DQ blocks |
Alarm 8-blocks | Yes |
● Number of instances for alarm 8 and S7 communication blocks, max. | 600 |
● preset, max. | 300 |
Process control messages | Yes |
Number of archives that can log on simultaneously (SFB 37 AR_SEND) | 16 |
Test commissioning functions | |
Status block | Yes |
Single step | Yes |
Number of breakpoints | 16 |
Status/control | |
● Status/control variable | Yes; Up to 16 variable tables |
● Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
● Number of variables, max. | 70 |
Forcing | |
● Forcing | Yes |
● Forcing, variables | Inputs/outputs, bit memories, distributed I/Os |
● Number of variables, max. | 256 |
Diagnostic buffer | |
● present | Yes |
● Number of entries, max. | 3 200 |
— adjustable | Yes |
— preset | 120 |
Service data | |
● can be read out | Yes |
EMC | |
Emission of radio interference acc. to EN 55 011 | |
● Limit class A, for use in industrial areas | Yes |
● Limit class B, for use in residential areas | No |
configuration / header | |
Configuration software | |
● STEP 7 | Yes |
configuration / programming / header | |
● Command set | see instruction list |
● Nesting levels | 7 |
● Access to consistent data in process image | Yes |
● System functions (SFC) | see instruction list |
● System function blocks (SFB) | see instruction list |
Programming language | |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
— SCL | Yes |
— CFC | Yes |
— GRAPH | Yes |
— HiGraph® | Yes |
configuration / programming / number of simultaneously active SFC / header | |
— RD_REC | 8 |
— WR_REC | 8 |
— WR_PARM | 8 |
— PARM_MOD | 1 |
— WR_DPARM | 2 |
— DPNRM_DG | 8 |
— RDSYSST | 8 |
— DP_TOPOL | 1 |
configuration / programming / number of simultaneously active SFB / header | |
— RDREC | 8 |
— WRREC | 8 |
Know-how protection | |
● User program protection/password protection | Yes |
● Block encryption | Yes; With S7 block Privacy |
Dimensions | |
Width | 50 mm |
Height | 290 mm |
Depth | 219 mm |
Weights | |
Weight, approx. | 995 g |
[/fusion_table]
Weight | 1.332 kg |
---|---|
Dimensions | 23.3 × 30 × 6.3 cm |
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penan
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)
inosaki.com 2008 -2024