Model |
EM DR16 |
EM DT16 |
EM DR32 |
EM DT32 |
Order No.: (MLFB) |
6ES7 288-2DR16-0AA0 |
6ES7 288-2DT16-0AA0 |
6ES7 288-2DR32-0AA0 |
6ES7 288-2DT32-0AA0 |
Dimension W x H x D (mm) |
45 x 100 x 81 |
70 x 100 x 81 |
Weight |
201.9 g |
179.7 g |
295.4 g |
257.3 g |
Power consumption |
5.5 W |
2.5 W |
10 W |
4.5 W |
Current consumption (SM bus) |
145 mA |
145 mA |
180 mA |
185 mA |
Current consumption (24 V DC) |
4 mA for each input point used |
Each relay coil used is 11 mA |
|
Each relay coil used is 11 mA |
|
|
Digital input |
Number of input points |
8 |
16 |
Type |
The sinking / sourcing type (IEC type 1 sinking) |
Rated voltage |
It is 24V DC when the current is 4 mA, nominal value |
Allowable continuous voltage |
Max 30 V DC |
Surge voltage |
35 V DC, lasting 0.5 s |
Logic 1 signal (min) |
15 V DC |
Logic 0 signal (min) |
5 V DC |
Isolation (field side and logic side) |
500 V AC, lasting 1 min |
Isolation group |
2 |
Filter time |
0.2, 0.4, 0.8, 1.6, 3.2, 6.4 and 12.8 ms (optional, 4 form one group) |
Number of inputs that connect at the same time |
8 |
|
Cable length |
500 m (Shielded), 150 m (non shielded) |
Digital output |
Number of output |
8 |
16 |
Type |
Relay, dry contact |
Solid state-MOSFET |
Relay, dry contact |
Solid state-MOSFET |
Voltage range |
5 ~ 30 V DC or 5 ~ 250 V AC |
20.4 ~ 28.8 V DC |
5 ~ 30 V DC or 5 ~ 250 V AC |
20.4 ~ 28.8 V DC |
Logic 1 signal when the current is max. |
– |
Min. 20 V DC |
– |
Min. 20 V DC |
Logic 0 signal when the load is KG |
– |
Max. 0.1 V DC |
– |
Max. 0.1 V DC |
Rated current at each point (max) |
2:00 AM |
0.75 A |
2:00 AM |
0.75 A |
Lamp load |
30 W DC/200 W AC |
5 W |
30 W DC/200 W AC |
5 W |
Resistance of the contact in the ON state |
New equipment is 0.2 Ω maximally |
Max. 0.6 Ω |
New equipment is 0.2 Ω maximally |
Max. 0.6 Ω |
Leakage current at each point |
– |
Max. 10 μ A |
– |
Max. 10 μ A |
Surge current |
It is 7A when the contact is closed |
8 A, max. lasting 100 ms |
It is 7A when the contact is closed |
8 A, max. lasting 100 ms |
Overload protection |
none |
|
|
|
Isolation (field side and logic side) |
1500 V AC, lasting 1 min (coil and contact) none, (coil and logic side) |
500 V AC, lasting 1 min |
1500 V AC, lasting 1 min (coil and contact) none, (coil and logic side) |
500 V AC, lasting 1 min |
Isolation resistance |
New equipment is 100 MΩ minimally |
– |
New equipment is 100 MΩ minimally |
– |
Disconnect the insulation between the contacts |
750 V AC, lasting 1 min |
– |
750 V AC, lasting 1 min |
– |
Isolated group |
2 |
2 |
4 |
3 |
Each end of the current public |
8:00 AM |
3:00 AM |
8:00 AM |
6:00 AM |
Inductive voltage clamp |
– |
-48 V |
– |
-48 V |
Switching delay |
Max.10 ms |
From the disconnection to connection max.50 μs from the connection to disconnection is 200 μs max. |
Max.10 ms. |
From the disconnection to connection max. 50 μs from the connection to disconnection is 200 μs max. |
Mechanical life (no load) |
10,000,000 break/close cycles |
– |
10,000,000 break/close cycles |
– |
Contact life under the rated load |
100,000 break/close cycles |
– |
100,000 break/close cycles |
– |
Output state under the STOP mode |
Last value or replicable value (The default value is 0) |
Number of output that are connected at the same time |
8 |
16 |
Cable length |
Shielded: 500 m; non shielded: 300 m |