Contact Us:
sales@inosaki.com
USD $ 236.90
Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my
In the power range of up to 100 W, QUINT POWER provides superior system availability in the smallest size. Preventative function monitoring and exceptional power reserves are available for applications in the low-power range.
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Article Number | 2904595 |
---|---|
Width | 22.5 mm |
Height | 106 mm |
Depth | 90 mm |
Installation distance right/left (active, passive) | 0 mm / 0 mm (POut ≤50 %) |
Installation distance right/left (passive) | 5 mm / 5 mm (POut ≥50% ) |
Installation distance right/left (active) | 15 mm / 15 mm (POut ≥50% ) |
Installation distance top/bottom (active, passive) | 30 mm / 30 mm (POut ≤50 %) |
Installation distance top/bottom (passive) | 30 mm / 30 mm (POut ≥50% ) |
Installation distance top/bottom (active) | 30 mm / 30 mm (POut ≥50% ) |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Degree of protection | IP20 |
---|---|
Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (start-up type tested) | -40 °C |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | ≤ 5000 m (> 2000 m, observe derating) |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Input voltage range | 100 V AC … 240 V AC -15 % … +10 % |
---|---|
110 V DC … 250 V DC -20 % … +40 % | |
Dielectric strength maximum | 300 V AC (60 s) |
Frequency range (fN) | 50 Hz … 60 Hz -10 % … +10 % |
Discharge current to PE | < 0.25 mA (264 V AC, 60 Hz) |
Current consumption | 0.37 A (100 V AC) |
0.3 A (120 V AC) | |
0.17 A (230 V AC) | |
0.16 A (240 V AC) | |
Nominal power consumption | 32.8 VA |
Inrush current | typ. 9.1 A (at 25 °C) |
Mains buffering time | typ. 52 ms (120 V AC) |
typ. 52 ms (230 V AC) | |
Input fuse | 3.15 A (slow-blow, internal) |
Recommended breaker for input protection | 6 A … 16 A (Characteristic B, C or comparable) |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Nominal output voltage | 5 V DC |
---|---|
Setting range of the output voltage (USet) | 5 V DC … 6.2 V DC (constant capacity) |
Nominal output current (IN) | 5 A |
Static Boost (IStat.Boost) | 6.25 A (≤ 40 °C) |
Dynamic Boost (IDyn.Boost) | 8 A (≤ 60 °C (5 s)) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback voltage resistance | ≤ 16 V DC (16 V e-caps in output circuit) |
Protection against overvoltage at the output (OVP) | < 8 V DC |
Control deviation | < 0.3 % (change in load, static 10 % … 90 %) |
< 3 % () | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 50 mVPP (with nominal values) |
Output power | 25 W |
Typical response time | 350 ms |
Maximum power dissipation in no-load condition | < 0.37 W (120 V AC) |
< 0.41 W (230 V AC) | |
Power loss nominal load max. | < 3.7 W (120 V AC) |
< 3.3 W (230 V AC) |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Net weight | 0.184 kg |
---|---|
Efficiency | typ. 87.4 % (120 V AC) |
typ. 88.4 % (230 V AC) | |
MTBF (IEC 61709, SN 29500) | > 1890000 h (25 °C) |
> 1080700 h (40 °C) | |
> 473300 h (60 °C) | |
Insulation voltage input/output | 4 kV AC (type test) |
3 kV AC (routine test) | |
Degree of protection | IP20 |
Protection class | II |
Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Connection method | Push-in connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Connection method | Push-in connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Connection method | Push-in connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 10 mm |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
EMC requirements, power plant | IEC 61850-3 |
---|---|
EN 61000-6-5 | |
Standard – Safety of power supply units up to 1100 V (insulation distances) | DIN EN 61558-2-16 |
Standard – Safety of transformers | EN 61558-2-16 |
Standard – Electrical safety | IEC 61010-1 (SELV) |
Standard – safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) | |
Standard – Safe isolation | IEC 61558-2-16 |
Standard – power supply devices for low voltage with DC output | EN 61204-3 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Rail applications | EN 50121-3-2 |
EN 50121-5 | |
IEC 62236-3-2 | |
IEC 62236-5 | |
Overvoltage category EN 61010-1 | II (≤ 5000 m) |
Overvoltage category EN 62477-1 | III (≤ 2000 m) |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
UL approvals | UL Listed UL 61010-1 |
---|---|
UL Listed UL 61010-2-201 | |
UL 1310 Class 2 Power Units | |
SIQ | CB-Scheme (IEC 61010-1, IEC 61010-2-201) |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
---|---|
Conducted noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Harmonic currents | EN 61000-3-2 |
EN 61000-3-2 (Class A) | |
Flicker | EN 61000-3-3 |
Electrostatic discharge | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Electromagnetic HF field | EN 61000-4-3 |
Frequency range | 80 MHz … 1 GHz |
Test field strength | 20 V/m (Test Level X) |
Frequency range | 1 GHz … 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst) | EN 61000-4-4 |
Input | 4 kV (Test Level 4 – asymmetrical) |
Output | 4 kV (Test Level X – asymmetrical) |
Signal | 4 kV (Test Level X – asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge) | EN 61000-4-5 |
Input | 2 kV (Test Level 4 – symmetrical) |
4 kV (Test Level 4 – asymmetrical) | |
Output | 1 kV (Test Level 3 – symmetrical) |
2 kV (Test Level 3 – asymmetrical) | |
Signal | 0.5 kV (Test Level 2 – symmetrical) |
Comments | Criterion A |
Conducted interference | EN 61000-4-6 |
I/O/S | asymmetrical |
Frequency range | 0.15 MHz … 80 MHz |
Voltage | 10 V (Test Level 3) |
Comments | Criterion A |
Power frequency magnetic field | EN 61000-4-8 |
Frequency | 16.67 Hz |
50 Hz | |
60 Hz | |
Test field strength | 100 A/m |
Additional text | 60 s |
Comments | Criterion A |
Frequency | 50 Hz |
60 Hz | |
Frequency range | 50 Hz … 60 Hz |
Test field strength | 1 kA/m |
Additional text | 3 s |
Frequency | 0 Hz |
Test field strength | 300 A/m |
Additional text | DC, 60 s |
Voltage dips | EN 61000-4-11 |
Voltage | 100 V AC |
Frequency | 60 Hz |
Voltage dip | 70 % |
Number of periods | 1 / 25 / 30 periods |
Additional text | Test Level 2 |
Comments | Criterion A |
Voltage dip | 40 % |
Number of periods | 10 / 50 periods |
Additional text | Test Level 2 |
Comments | Criterion A |
Voltage dip | 0 % |
Number of periods | 0.5 / 1 / 5 / 50 periods |
Additional text | Test Level 2 |
Comments | Criterion B |
Pulse-shape magnetic field | EN 61000-4-9 |
Test field strength | 1000 A/m |
Comments | Criterion A |
Attenuated sinusoidal oscillations (ring wave) | EN 61000-4-12 |
Input | 2 kV (symmetrical) |
4 kV (asymmetrical) | |
Comments | Criterion A |
Asymmetrical conducted disturbance variables | EN 61000-4-16 |
Test level 1 | 16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3) |
Voltage | 30 V (10 s) |
Test level 2 | 16.67 Hz 50 Hz 60 Hz (Test Level 2) |
Voltage | 300 V (1 s) |
Comments | Criterion A |
Attenuated oscillating wave | EN 61000-4-18 |
Voltage | 1 kV (symmetrical) |
2.5 kV (asymmetrical) | |
1 kV (symmetrical) | |
Comments | Criterion A |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”1ps” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
REACh SVHC | Lead 7439-92-1 |
---|
[/fusion_table]
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penan
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)
inosaki.com 2008 -2024