Contact Us:
sales@inosaki.com

QUINT-PS/24DC/24DC/10 – 2320092 – Phoenix Contact DC/DC Converters

$ 510.60

SKU Phoenix Contact 2320092 Category

Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to  PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my

 

Product Description

QUINT DC/DC converter with maximum functionality
DC/DC converters alter the voltage level, regenerate the voltage at the end of long cables or enable the creation of independent supply systems by means of electrical isolation.
QUINT DC/DC converters magnetically and therefore quickly trip circuit breakers with six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.

 

Dimensions

Width 48 mm
Height 130 mm
Depth 125 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm (≤ 70 °C)
Installation distance right/left (active) 15 mm / 15 mm (≤ 70 °C)
Installation distance top/bottom 50 mm / 50 mm (≤ 70 °C)
Installation distance top/bottom (active) 50 mm / 50 mm (≤ 70 °C)

 

Alternative assembly

Width 122 mm
Height 130 mm
Depth 51 mm

 

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C … 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested)
Ambient temperature (storage/transport) -40 °C … 85 °C
Ambient temperature (start-up type tested) -40 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 5 Hz, amplitude ±1.6 mm (according to IEC 60068-2-6)
5 Hz … 100 Hz, 4g, 90 min.

 

 

Input data

Nominal input voltage range 24 V DC
Input voltage range 18 V DC … 32 V DC
Extended input voltage range in operation 14 V DC … 18 V DC (Derating)
Wide-range input no
Input voltage range DC 18 V DC … 32 V DC
14 V DC … 18 V DC (Consider derating during operation)
Voltage type of supply voltage DC
Inrush current < 15 A (typical)
Inrush current integral (I2t) < 2.7 A2s
Mains buffering time > 12 ms (24 V DC)
Current consumption 14 A (24 V, IBOOST)
Reverse polarity protection ≤ 30 V DC
Protective circuit Transient surge protection; Varistor
Input fuse 25 A (internal (device protection))
Recommended breaker for input protection 16 A … 20 A (Characteristics B, C, D, K)

 

Output data

Efficiency > 92 %
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (-25 °C … 60 °C)
POWER BOOST (IBoost) 12.5 A (-25 °C … 40 °C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 60 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6 / C2 / C4
Derating 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) < 35 V DC
Max. capacitive load unlimited
Active current limitation Approx. 18 A
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 2 % (change in load, dynamic 10 % … 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP
Output power 240 W
Peak switching voltages nominal load < 10 mVPP (20 MHz)
Maximum no-load power dissipation 1.6 W
Power loss nominal load max. 24 W
Rise time < 2 ms (UOUT (10 % … 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
2 (Devices)

 

Signal: DC OK active

Output description UOUT > 0.9 x UN: High signal
Switching voltage range 18 V DC … 24 V DC
Maximum inrush current < 20 mA (short-circuit-proof)

 

Signal: POWER BOOST, active

Output description IOUT < IN: High signal
Switching voltage range 18 V DC … 24 V DC
Maximum inrush current < 20 mA (short-circuit-proof)

 

Signal: UIN OK, active

Output description UIN > 19.2 V: High signal
Switching voltage range 18 V DC … 24 V DC
Maximum inrush current ≤ 20 mA (short-circuit-proof)

 

Signal: DC OK floating

Output description Relay
Output voltage ≤ 30 V AC/DC
Maximum inrush current ≤ 100 mA

 

General

Item number 2320092
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CM05
Product Key CMDQ43
Catalog Page Page 248 (C-4-2017)
GTIN 4046356481885
Weight per Piece (including packing) 1,162.5 g
Weight per Piece (excluding packing) 900 g
Customs tariff number 85044083
Country of origin IN

 

Connection data, input

Connection method Pluggable screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 8 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

 

Connection data, output

Connection method Pluggable screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

 

Connection data for Signal

Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm

 

Standards and Regulations

Rail applications EN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)
Standard – Safe isolation DIN VDE 0100-410

 

Approvals

Shipbuilding approval DNV GL (EMC B)
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)

 

EMC data

EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz … 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1 GHz … 2 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 2 GHz … 3 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (Test Level 3 – asymmetrical)
Output 2 kV (Test Level 3 – asymmetrical)
Signal 2 kV (Test Level 4 – asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 1 kV (Test Level 2 – symmetrical)
2 kV (Test Level 3 – asymmetrical)
Output 1 kV (Test Level 2 – symmetrical)
2 kV (Test Level 3 – asymmetrical)
Signal 1 kV (Test Level 2 – asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 0.15 MHz … 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Additional information

Weight 0.900 kg
Dimensions 12.50 × 4.8 × 13.00 cm

Related Products

IDS Camera IDS imaging ueye camera
SCHNEIDER_AC Servo Driver_A6NE
Panasonic_OS-EX10-15
PD8-02PD14 16-03 0406
Banner_Q453EQ
IDS_Cameras_Accessories_AL00100
Select your currency