Contact Us:
sales@inosaki.com
USD $ 427.06 – USD $ 1,187.72
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Product name |
Specification | Model | ||||||
---|---|---|---|---|---|---|---|---|
Number of points |
Input type |
Res- olution (25°C) |
Over all accuracy (25°C) |
Con- ver- sion time |
I/O re- freshing method |
Termi- nals |
||
Thermo- couple Input type |
2 points |
Thermo- couple |
0.1°C max. *1 |
Refer to the Reference accuracy and temperature coefficient according to the input type and measurement temperature. |
250 ms/ Unit |
Free- Run re- freshing |
16 Terminals |
NX-TS2101 |
4 points |
16 Ter- minals x 2 |
NX-TS3101 | ||||||
2 points |
0.01°C max. |
10 ms/ Unit |
16 Terminals |
NX-TS2102 | ||||
4 points |
16 Ter- minals x 2 |
NX-TS3102 | ||||||
2 points |
0.001°C max. |
60 ms/ Unit |
16 Terminals |
NX-TS2104 | ||||
4 points |
16 Ter- minals x 2 |
NX-TS3104 | ||||||
Resist- ance Ther- mometer Input type |
2 points |
Resist- ance Ther- mometer (Pt100/ Pt1000, three- wire) *2 |
0.1°C max. |
250 ms/ Unit |
16 Terminals |
NX-TS2201 | ||
4 points |
16 Ter- minals x 2 |
NX-TS3201 | ||||||
2 points |
0.01°C max. |
10 ms/ Unit |
16 Terminals |
NX-TS2202 | ||||
4 points |
16 Ter- minals x 2 |
NX-TS3202 | ||||||
2 points |
0.001°C max. |
60 ms/ Unit |
16 Terminals |
NX-TS2204 | ||||
4 points |
16 Ter- minals x 2 |
NX-TS3204 |
[/fusion_table]
*1. The resolution is 0.2°C max. when the input type is R, S, or W.
*2. The NX-TS2202 and NX-TS3202 only support Pt100 three-wire sensor
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Item | Specification | |
---|---|---|
Enclosure | Mounted in a panel | |
Grounding method | Ground to 100 Ω or less | |
Operating environment |
Ambient operating temperature |
0 to 55°C |
Ambient operating humidity |
10% to 95% (with no condensation or icing) | |
Atmosphere | Must be free from corrosive gases. | |
Ambient storage temperature |
-25 to 70°C (with no condensation or icing) | |
Altitude | 2,000 m max. | |
Pollution degree | 2 or less: Meets IEC 61010-2-201. | |
Noise immunity | 2 kV on power supply line (Conforms to IEC61000-4-4.) | |
Overvoltage category | Category II: Meets IEC 61010-2-201. | |
EMC immunity level | Zone B | |
Vibration resistance | Conforms to IEC 60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, acceleration of 9.8 m/s2, 100 min each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) |
|
Shock resistance | Conforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions | |
Applicable standards * | cULus: Listed (UL508), ANSI/ISA 12.12.01, EU: EN 61131-2, C-Tick or RCM, KC Registration, NK, LR |
[/fusion_table]
* Ask your OMRON representative for the most recent applicable standards for each model.
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Model Name | NX-TS2102 | NX-TS2104 | NX-TS2201 | NX-TS2202 | NX-TS2204 | NX-TS3102 |
I/O system | NX I/O Bus | NX I/O Bus | NX I/O Bus | NX I/O Bus | NX I/O Bus | NX I/O Bus |
Type of module | Analog I/O | Analog I/O | Analog I/O | Analog I/O | Analog I/O | Analog I/O |
Number of analog inputs | 2 | 2 | 2 | 2 | 2 | 4 |
Temperature input type | B, C (WRe5-26), E, J, K, L, N, P (PLII), R, S, T, U | B, C (WRe5-26), E, J, K, L, N, P (PLII), R, S, T, U | Pt100, Pt1000 | Pt100 | Pt100, Pt1000 | B, C (WRe5-26), E, J, K, L, N, P (PLII), R, S, T, U |
Linear analog input type | None | None | None | None | None | None |
Resolution of the analog inputs | 17 Bit | 20 Bit | 14 Bit | 17 Bit | 20 Bit | 17 Bit |
Input circuit type | Differential | Differential | Single-ended | Single-ended | Single-ended | Differential |
Number of analog outputs | 0 | 0 | 0 | 0 | 0 | 0 |
Linear analog output type | None | None | None | None | None | None |
Conversion time | 10 ms/unit | 60 ms/unit | 250 ms/unit | 10 ms/unit | 60 ms/unit | 10 ms/unit |
Signal processing | Free running | Free running | Free running | Free running | Free running | Free running |
IO-Link master | ✘ | ✘ | ✘ | ✘ | ✘ | ✘ |
I/O connection type | Push-in | Push-in | Push-in | Push-in | Push-in | Push-in |
Number of I/O connectors | 1 | 1 | 1 | 1 | 1 | 2 |
Detachable I/O connector | ✔ | ✔ | ✔ | ✔ | ✔ | ✔ |
Suitable for safety functions | ✘ | ✘ | ✘ | ✘ | ✘ | ✘ |
SIL according to IEC 61508 | None | None | None | None | None | None |
Degree of protection (IP) | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 |
Product Height (unpacked) | 100 mm | 100 mm | 100 mm | 100 mm | 100 mm | 100 mm |
Product Width (unpacked) | 12 mm | 12 mm | 12 mm | 12 mm | 12 mm | 24 mm |
Product Depth (unpacked) | 80 mm | 80 mm | 80 mm | 80 mm | 80 mm | 80 mm |
Product Weight (unpacked) | 70 g | 70 g | 70 g | 70 g | 70 g | 140 g |
[/fusion_table]
[fusion_table fusion_table_type=”1″ fusion_table_rows=”” fusion_table_columns=”” margin_top=”” margin_right=”” margin_bottom=”” margin_left=”” hide_on_mobile=”small-visibility,medium-visibility,large-visibility” class=”” id=”” animation_type=”” animation_direction=”left” animation_color=”” hue=”” saturation=”” lightness=”” alpha=”” animation_speed=”0.3″ animation_delay=”0″ animation_offset=””]
Model Name | NX-TS3104 | NX-TS3201 | NX-TS3202 | NX-TS3204 | NX-TS2101 |
I/O system | NX I/O Bus | NX I/O Bus | NX I/O Bus | NX I/O Bus | NX I/O Bus |
Type of module | Analog I/O | Analog I/O | Analog I/O | Analog I/O | Analog I/O |
Number of analog inputs | 4 | 4 | 4 | 4 | 2 |
Temperature input type | B, C (WRe5-26), E, J, K, L, N, P (PLII), R, S, T, U | Pt100, Pt1000 | Pt100 | Pt100, Pt1000 | B, C (WRe5-26), E, J, K, L, N, P (PLII), R, S, T, U |
Linear analog input type | None | None | None | None | None |
Resolution of the analog inputs | 20 Bit | 14 Bit | 17 Bit | 20 Bit | 14 Bit |
Input circuit type | Differential | Single-ended | Single-ended | Single-ended | Differential |
Number of analog outputs | 0 | 0 | 0 | 0 | 0 |
Linear analog output type | 0 Bit | None | None | None | None |
Conversion time | 60 ms/unit | 250 ms/unit | 10 ms/unit | 60 ms/unit | 250 ms/unit |
Signal processing | Free running | Free running | Free running | Free running | Free running |
IO-Link master | ✘ | ✘ | ✘ | ✘ | ✘ |
I/O connection type | Push-in | Push-in | Push-in | Push-in | Push-in |
Number of I/O connectors | 2 | 2 | 2 | 2 | 1 |
Detachable I/O connector | ✔ | ✔ | ✔ | ✔ | ✔ |
Suitable for safety functions | ✘ | ✘ | ✘ | ✘ | ✘ |
SIL according to IEC 61508 | None | None | None | None | None |
Degree of protection (IP) | IP20 | IP20 | IP20 | IP20 | IP20 |
Product Height (unpacked) | 100 mm | 100 mm | 100 mm | 100 mm | 100 mm |
Product Width (unpacked) | 24 mm | 24 mm | 24 mm | 24 mm | 12 mm |
Product Depth (unpacked) | 80 mm | 80 mm | 80 mm | 80 mm | 80 mm |
Product Weight (unpacked) | 140 g | 140 g | 140 g | 140 g | 70 g |
[/fusion_table]
Weight | N/A |
---|---|
Dimensions | N/A |