Item |
H7CC-A8/-A11[] |
H7CC-A[] |
H7CC-AW[]/AU[] |
Classification |
Preset counter |
Preset counter/ tachometer |
Configuration |
1-stage preset counter, 1-stage preset counter with total counter (selectable) *1 |
1-stage/2-stage preset counter,
total and preset counter *1,
batch counter, dual counter,
twin counter, and tachometer
(selectable) |
Ratings |
Power supply
voltage *2 |
• 100 to 240 VAC, 50/60 Hz
• 24 VAC, 50/60 Hz or 12 to 48 VDC |
Operating
voltage
fluctuation
range |
85% to 110% of rated supply voltage (12 to 48 VDC: 90% to 110%) |
Power
consumption |
Approx. 6.8 VA at 100 to 240 VAC,
Approx. 5.5 VA/3.3 W at 24 VAC/12 to 48 VDC, |
Mounting method |
Flush mounting or surface mounting |
Flush mounting |
External connections |
8-pin/ 11-pin socket |
Screw terminals |
Degree of protection |
IEC IP66 for panel surface only and only when Y92S-P6 Waterproof Packing is used. |
Input signals |
CP1, CP2, reset, and total reset *4 |
CP1, CP2, reset 1, and reset 2 |
Counter |
Maximum
counting
speed |
30 Hz (minimum pulse width: 16.7 ms) or 10 kHz (minimum pulse width: 0.05 ms) (selectable) (ON/OFF ratio 1:1)
*Common setting for CP1 and CP2 |
Input
mode |
Increment (UP), decrement (DOWN), increment/decrement (UP/DOWN A (command input), UP/DOWN B (individual inputs), or UP/DOWN C (quadrature inputs)), UP/DOWN D (command input), UP/DOWN E (individual inputs), UP/DOWN E (quadrature inputs) |
Output
mode |
N, F, C, R, K-1, P, Q, A, K-2, D, and L. |
N, F, C, R, K-1, P, Q, A, K-2, D, L, and H. |
One-shot
out put
time |
0.01 to 99.99 s |
Reset
system |
External (minimum reset signal width: 1 ms or 20 ms, selectable), manual, and automatic reset (internal according to C, R, P, and Q mode operation) |
Tachometer |
Refer to the tachometer function ratings. |
Prescaling function |
Yes (0.001 to 99.999) |
Decimal point adjustment |
Yes (right most 3 digits) |
Sensor waiting time |
290 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.) |
Input method |
No-voltage (NPN) input/voltage (PNP) input (switchable)
No-voltage inputs:
ON impedance: 1 kΩ max. (Leakage current: 12 mA at 0 Ω) ON residual voltage: 3 V max.
OFF impedance: 100 kΩ min.
Voltage input:
High (logic) level: 4.5 to 30 VDC
Low (logic) level: 0 to 2 VDC (Input resistance: approx. 4.7 kΩ) |
External power supply |
12 VDC (±10%), 100 mA (except for H7CC-A8[] models) Refer to Precautions for Correct Use on Catalog for details. |
Control output |
• Contact output: 3 A at 250 VAC/30 VDC, resistive load (cosφ=1),
Minimum applied load: 10 mA at 5 VDC (failure level: P, reference value)
• Transistor output: NPN open collector, 100 mA at 30 VDC, Residual voltage: 1.5 VDC max. (approx. 1 V),
Leakage current: 0.1 mA max. |
Display *3 |
7-segment, negative transmissive LCD
Character height
Count value: 10 mm (white)
Set value: 6 mm (green) |
Digits |
6 digits
-99999 to 999999
(-5 digits to +6 digits) |
6 digits
-99999 to 999999
(-5 digits to +6 digits),
tachometer: 0 to 999999 |
Memory backup |
Non-volatile memory (overwrites: 100,000 times min.) that can store data for 10 years min. |
Operating temperature range |
-10 to 55°C (-10 to 50°C if Counter/Tachometers are mounted side by side) (with no icing or condensation) |
Storage temperature range |
-25 to 70°C (with no icing or condensation) |
Operating humidity range |
25% to 85% |
Case color |
Black (N1.5) |
Attachments |
— |
Flush mounting adapter, waterproof packing, terminal cover |