NX-ILM400 – NX-series – Omron IO-Link Master Unit

$ 257.83

SKU NX-ILM400 Category

NX-series IO-Link Master Unit

Product name Specification Model
Number of
IO-Link ports
I/O refreshing
method
I/O connection
terminals
NX-series IO-Link Master Unit 4 Free-Run refreshing Screwless clamping
terminal block
NX-ILM400

 

General Specification

Item Specification
Enclosure Must be built into a panel.
Grounding methods Ground to 100 Ω or less.
Operating
environment
Ambient operating
temperature
0 to 55°C
Ambient operating
humidity
10% to 95% (with no condensation or icing)
Atmosphere Must be free from corrosive gases.
Ambient storage
temperature
-25 to 70°C (with no condensation or icing)
Altitude 2,000 m max.
Pollution degree Pollution degree 2 or less: Meets IEC 61010-2-201.
Noise immunity Conforms to IEC 61000-4-4, 2 kV (power line).
Overvoltage
category
Category: Meets IEC 61010-2-201.
EMC immunity level Zone B
Vibration resistance Conforms to IEC 60068-2-6.
5 to 8.4 Hz with amplitude of 3.5 mm,
8.4 to 150 Hz, acceleration of 9.8 m/s2
100 min each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
Shock resistance Conforms to IEC 60068-2-27. 147 m/s2, 3 times each in X, Y, and Z directions
Applicable standards * UL 61010-2-201, ANSI/ISA 12.12.01, EU: EN 61131-2, NK, LR, RCM, KC,
and IO-Link conformance

 

* Ask your OMRON representative for the most recent applicable standards for each model.

 

Unit Specification

Item Specification
Unit name IO-Link Master Unit
Model NX-ILM400
Number of ports 4
Communications
specifications
Communications protocol IO-Link protocol
Baud rate COM1: 4.8kbps
COM2: 38.4kbps
COM3: 230.4kbps
Topology 1:1
Compliant standards • IO-Link Interface and System Specification Version1.1.2
• IO-Link Test Specification Version1.1.2
Power supply to
devices* in
IO-Link Mode or
SIO (DI) Mode
Rated voltage 24 VDC (20.4 to 28.8 VDC)
Maximum load current 0.2 A/port
Short-circuit protection Provided.
Digital inputs
(in SIO (DI)
Mode)
Internal I/O common PNP
Rated voltage 24 VDC (20.4 to 28.8 VDC)
Input current 5 mA typical (24 VDC)
ON voltage/ON current 15 VDC min., 2 mA min.
OFF voltage 5 VDC max.
Input filter time No filter, 0.25 ms, 0.5 ms, 1 ms (default), 2 ms, 4 ms, 8 ms, 16 ms,
32 ms, 64 ms,128 ms, 256 ms
Digital outputs
(in SIO (DO)
Mode)
Internal I/O common PNP
Output type Push-pull
Rated voltage 24 VDC (20.4 to 28.8 VDC)
Maximum load current 0.1 A/port
Short-circuit protection Provided.
Leakage current 0.1 mA max.
Residual voltage 1.5 V max.
Digital inputs
for pin 2
(in IO-Link
Mode)
Internal I/O common PNP
Rated voltage 24 VDC (20.4 to 28.8 VDC)
Input current 2 mA typical (24 VDC)
ON voltage/ON current 15 VDC min., 2 mA min.
OFF voltage 5 VDC max.
Input filter time No filter, 0.25 ms, 0.5 ms, 1 ms (default), 2 ms, 4 ms, 8 ms, 16 ms,
32 ms, 64 ms, 128ms, 256 ms
Cable
specifications
Cable type Unshielded
Length 20 m max.
Electrostatic capacity
between lines
3 nF max.
Loop resistance 6 Ω max.
External connection terminals Screwless Clamping Terminal Block (16 terminals)
I/O refreshing method Free-Run refreshing
Dimensions 12 × 100 × 71 mm (W × H × D)
Isolation method Photocoupler isolation
Insulation resistance 20 MΩ min. at 100 VDC (between isolated circuits)
Dielectric strength 510 VAC for 1 min, leakage current: 5 mA max. (between isolated
circuits)
I/O power supply method Supply from the NX bus
NX Unit power consumption • Connected to a CPU Unit
1.05 W max.
• Connected to a Communications Coupler Unit
0.80 W max.
Current consumption from I/O power supply 50 mA
Weight 67 g
Circuit configuration 3540_sp_2_1
Terminal connection diagram 3540_sp_2_2
Installation orientation and restrictions 3540_sp_2_3
Protective functions L+ terminal short-circuit protection
C/Q terminal short-circuit protection

 

 

Function Specifications

Function Description
Communications Cyclic
communications
I/O data (process data) in the IO-Link devices is cyclically exchanged with the IO-Link Master Unit as the IO-Link communications master.
At the same time, this data and the status of the IO-Link Master Unit is cyclically exchanged with the controller, with the IO-Link Master Unit operating as a slave of the controller.
Cyclic communications can be used to check the amount of detection performance deterioration in devices, and to check changes in usage conditions, such as the amount of incident light for photoelectric sensors, stability detection margins, and excessive proximity for proximity sensors.
Message
communications
The controller can send messages (commands) to the IO-Link Master Unit and receive the response from the IO-Link Master Unit.
The IO-Link Master Unit can also function as a gateway to send messages (commands and responses) between the controller and the IO-Link devices.
During operation, you can change and adjust device parameters, such as threshold settings, tuning execution, and ON-delay time changes, from a program.
Or, during operation, you can check the internal status, such as the operating times of devices.
Communications mode settings You can select any of the following modes for each port:
IO-Link Mode, SIO (DI) Mode, SIO (DO) Mode, and Disable Port
This allows you to combine IO-Link communications and digital I/O in a single unit.
Digital inputs for pin 2 In IO-Link Mode, you can perform digital input with pin 2 while performing IO-Link communications.
Automatic baud rate setting for
IO-Link communications
The IO-Link Master Unit automatically matches the specific baud rates (COM1, COM2, or COM3) of the IO-Link devices to communicate with the IO-Link devices.
Therefore, it is not necessary to set the baud rate of the connected device for each port.
Connected device verification This function is used to verify the configuration of IO-Link devices that are connected to the IO-Link Master Unit against the registered IO-Link device configuration settings when the power supply is turned ON.
The user can enable or disable connected device verification.
IO-Link communications error
detection
This function detects I/O cable breaks, disconnections from IO-Link device ports, error-level device events, device configuration verification errors, and IO-Link device malfunctions.
Detection of short-circuits in I/O
cables
This function detects short-circuits in I/O cables
Notification of input data validity The controller can use the Input Data Enabled Flags to determine whether the process input data for IO-Link communications is valid.
Load rejection for controller
communications error
This function turns OFF outputs from the IO-Link Master Unit when a communications error occurs in communications with the controller in IO-Link Mode or in an SIO mode.
This prevents incorrect output operations when communications error occurs.
IO-Link total communications lost
frames
The IO-Link total communications lost frames can be read from the CX-ConfiguratorFDT.
You can use this function to determine communications status as affected by I/O cable noise or other factors.
Digital input filter This function is used to eliminate chattering and noise of the input signal for digital inputs in SIO(DI) Mode or for digital inputs for pin 2 in IO-Link Mode. It prevents data change and stabilizes the input signal even in situations where the input data changes due to chattering or noise and the bit status is unstable.
Digital input collection* In IO-Link Mode, this function reflects the specified bit data in the input data from the IO-Link device on the digital input data of the IO-Link Master Unit. As a result, the bit data in the input data from the IO-Link device can be aggregated into the digital input data of the IO-Link Master Unit. One bit for each IO-Link port can be aggregated. This function cannot be used in SIO (DI) Mode and SIO (DO) Mode.
If you use this function, digital inputs with pin 2 cannot be used.
Backup and restoration of
parameter settings in IO-Link
devices
This function is used to back up parameter settings in IO-Link devices in the IO-Link Master Unit or restore them to IO-Link devices.
This eliminates the need to set parameters again after replacing an IO-Link device.
Event log This function records events, such as errors and status changes, that occur in the IO-Link Master Unit and the IO-Link devices.
This enables partial troubleshooting for NJ/NX-series Controllers and NY-series Industrial PCs.

 

* This function is supported with the unit version 1.1 or later.

Additional information

Weight 0.067 kg
Dimensions 10.6 × 1.2 × 8 cm