$ 197.34 – $ 210.91
Product Name | Power supply voltage |
Output current | Output capacity |
Options | Model | ||||
---|---|---|---|---|---|---|---|---|---|
5-VDC output capacity |
24-VDC output capacity |
Total power consump- tion |
24-VDC service power supply |
RUN output |
Main- tenance forecast monitor |
||||
AC Power Supply Unit |
100 to 240 VAC |
6.0 A | 1.0 A | 30 W | No | Yes | No | NJ-PA3001 | |
DC Power Supply Unit |
24 VDC | NJ-PD3001 |
Note: Power supply units for the CJ-Series cannot be used as a power supply for a CPU rack of the NJ system or as a
power supply for an expansion rack.
Item | Specifications | |
---|---|---|
Model | NJ-PA3001 | NJ-PD3001 |
Supply voltage | 100 to 240 VAC (wide-range), 50/60 Hz | 24 VDC |
Operating voltage and frequency ranges |
85 to 264 VAC, 47 to 63 Hz | 19.2 to 28.8 VDC |
Power consumption | 120 VA max. | 60 W max. |
Inrush current *1 | At 100 VAC: 20 A/8 ms max. for cold start at room temperature At 200 VAC: 40 A/8 ms max. for cold start at room temperature |
At 24 VDC: 30 A/20 ms max. for cold start |
Output capacity *2 | 5 VDC, 6.0 A (including supply to CPU Unit using CPU Rack) 5 VDC, 6.0 A (using Expansion Rack) 24 VDC, 1.0 A Total: 30 W max. |
|
Output terminal (service supply) |
Not provided | |
RUN output *3 | Contact configuration: SPST-NO Switch capacity: 250 VAC, 2 A (resistive load) 120 VAC, 0.5 A (inductive load), 24 VDC, 2A (resistive load) |
|
Replacement notification function |
Not provided | |
Insulation resistance *4 |
20 MΩ min. (at 500 VDC) between AC external and GR terminals |
20 MΩ min. (at 500 VDC) between DC external and GR terminals |
Dielectric strength *4 *5 |
2,300 VAC 50/60 Hz for 1 min between AC external and GR terminals Leakage current: 10 mA max. |
1,000 VAC 50/60 Hz for 1 min between DC external and GR terminals Leakage current: 10 mA max. |
Noise immunity | 2 kV on power supply line (Conforms to IEC 61000-4-4.) | |
Vibration resistance | 5 to 8.4 Hz, 3.5-mm amplitude, 8.4 to 150 Hz, acceleration: 9.8 m/s2 in X, Y, and Z directions for 100 min (Time coefficient: 10 min × coefficient factor 10 = total time 100 min) (according to IEC 60068-2-6) |
|
Shock resistance | 147 m/s2 3 times each in X, Y, and Z directions (Relay Output Unit: 100 m/s2) (according to IEC 60068-2-27) |
|
Ambient operating temperature |
0 to 55°C | |
Ambient operating humidity |
10% to 90% (with no condensation) | |
Atmosphere | Must be free from corrosive gases. | |
Ambient storage temperature |
-20 to 75°C | |
Grounding | Less than 100 Ω | |
Enclosure | Mounted in panel | |
Weight | 470 g max. | 490 g max. |
CPU Rack dimensions | 174.7 to 484.7 × 90 × 90 mm (W × D × H) (not including cables) W = 70 (Power Supply Unit) + 90 (CPU Unit) + 20 × n + 31 × m + 14.7 (end cover) n is the number of 32-point I/O Units or I/O Control Units and m is the number of other Units. |
|
Safety measures | Conforms to cULus, EC Directives, NK, LR, RCM, and KC. |
*1. The AC and DC values above are given for a cold start, and the AC values are at room temperature. The AC inrush
control circuit uses a thermistor element with a low-temperature current control characteristic. If the ambient
temperature is high or the Controller is hot-started, the thermistor will not be sufficiently cool, and the inrush
current given in the table may be exceeded by up to twice the given value. The DC inrush control circuit uses a
capacitor-charging delay circuit. If the power is OFF for only a short time for a hot-start, the capacitor will not
sufficiently discharge and the inrush current given in the table may be exceeded by up to twice the given value. An
inrush current of approximately 4 A may occur and continue for 1 s when the power is turned ON. When selecting
fuses, breakers, and external DC power supply devices for external circuits, allow sufficient margin in shut-off
performance.
*2. Internal components in the Power Supply Unit will deteriorate or be damaged if the Power Supply Unit is used for an
extended period of time exceeding the power supply output capacity or if the outputs are shorted.
*3. Supported only when mounted to CPU Rack.
*4. The tests can also be performed with the LG terminal and GR terminal connected to each other.
*5. Change the applied voltage gradually using the adjuster on the Tester. If the full dielectric strength voltage is applied
or turned OFF using the switch on the Tester, the generated impulse voltage may damage the Power Supply Unit.
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penan
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)