S8VK-X – Without Indication Monitor – Omron Switch Mode Power Supply
USD $ 261.58 – USD $ 667.70
Ratings, Characteristics, and Functions
Power rating | 30 W | 60W | |||
---|---|---|---|---|---|
Rated output voltage (DC) | 5 V | 12 V | 24 V | ||
Indication monitor | None | None | None | ||
Efficiency * | 115 VAC input | 78% typ. | 85% typ. | 85% typ. | |
230 VAC input | 77% typ. | 86% typ. | 86% typ. | ||
Input conditions |
Voltage range * | Single-phase, 85 to 264 VAC, 90 to 350 VDC, 265 to 300 VAC (1 second) |
|||
Frequency * | 50/60 Hz (47 to 450 Hz) | ||||
Input current * | 115 VAC input | 0.53 A typ. | 0.99 A typ. | 1.1 A typ. | |
230 VAC input | 0.32 A typ. | 0.61 A typ. | 0.67 A typ. | ||
Power factor * | — | ||||
Leakage current * |
115 VAC input | 0.5 mA max. | |||
230 VAC input | 1 mA max. | ||||
Inrush current * |
115 VAC input | 16 A typ. | |||
230 VAC input | 32 A typ. | ||||
Output characteristics |
Rated output current | 5 A | 4.5 A | 2.5 A | |
Rated output power | 25 W | 54 W | 60 W | ||
Maximum boost current | 6 A | 5.4 A | 3 A | ||
Voltage adjustment range * | 4.5 to 5.8V (with V. ADJ) | 10.8 to 14 V (with V. ADJ) | 21.6 to 28 V (with V. ADJ) | ||
Ripple noise voltage * |
100 to 240 VAC input |
130 mVp-p max. at 20 MHz of bandwidth |
120 mVp-p max. at 20 MHz of bandwidth |
110 mVp-p max. at 20 MHz of bandwidth |
|
Input variation influence * | 0.5% max. | ||||
Load variation influence * | 1.5% max. | ||||
Temperature variation influence |
100 to 240 VAC input |
0.05%/°C max. | |||
Start up time * | 115 VAC input | 1000 ms max. | 1000 ms max. | 1000 ms max. | |
230 VAC input | 1000 ms max. | 1000 ms max. | 1000 ms max. | ||
Hold time * | 115 VAC input | 45 ms typ. | 20 ms typ. | 20 ms typ. | |
230 VAC input | 240 ms typ. | 120 ms typ. | 110 ms typ. | ||
Additional functions |
Overload protection | Yes, automatic reset, intermittent operation type, Refer to Overload Protection on catalog for details. |
|||
Overvoltage protection | Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again), Refer to Overvoltage Protection on catalog for details. |
||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | ||||
Parallel operation | Yes (For up to two Power Supplies), Refer to Parallel Operation on catalog for details. |
||||
Output indicator | Yes (LED: Green) | ||||
Alarm indicator | Yes (LED: Red) | ||||
Indication monitor |
Measurement and display details |
Refer to Communication and Indication Items on catalog for details. | |||
Main display | None | ||||
Ethernet communication |
Measurement and display details |
Refer to Communication and Indication Items on catalog for details. | |||
Communication protocol |
EtherNet/IP, Modbus TCP | ||||
Physical layer | 100BASE-TX | ||||
Communication specifications |
Refer to Communication Specifications on catalog for details. | ||||
Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals and output terminals, all EtherNet/IP ports), current cutoff 20 mA |
|||
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA |
|||||
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 30 mA |
|||||
0.5 kVAC for 1 min. (between all output terminals and all EtherNet/IP ports), current cutoff 30 mA |
|||||
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
||||
100 MΩ min. (between all EtherNet/IP ports and all input terminals) at 500 VDC |
|||||
Environment | Ambient operating temperature * | -40 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing) |
|||
Storage temperature | -40 to 85°C (with no condensation or icing) | ||||
Ambient operating humidity | 95% max. (Storage humidity: 95% max.) | ||||
Vibration resistance | 10 to 55 Hz, maximum 5 G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions |
||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||||
Reliability | MTBF * | 160,000 hrs typ. | |||
Life expectancy * | 10 years min. | ||||
Construction | Weight | 250 g max. | 250 g max. | 250 g max. | |
Cooling fan | No | ||||
Degree of protection | IP20 by EN/IEC 60529 |
Power rating | 90 W | 120 W | ||||
---|---|---|---|---|---|---|
Rated output voltage (DC) | 24 V | 24 V | ||||
Indication monitor | Included | None | Included | None | ||
Efficiency * | 115 VAC input | 86% typ. | 87% typ. | 90% typ. | 90% typ. | |
230 VAC input | 87% typ. | 88% typ. | 92% typ. | 92% typ. | ||
Input conditions |
Voltage range * | Single-phase, 85 to 264 VAC, 90 to 350 VDC, 265 to 300 VAC (1 second) |
||||
Frequency * | 50/60 Hz (47 to 450 Hz) | 50/60 Hz (47 to 63 Hz) | ||||
Input current * | 115 VAC input | 1.7 A typ. | 1.7 A typ. | 1.2 A typ. | 1.2 A typ. | |
230 VAC input | 1.0 A typ. | 1.0 A typ. | 0.63 A typ. | 0.63 A typ. | ||
Power factor * | — | 0.9 min. | ||||
Leakage current * |
115 VAC input | 0.5 mA max. | ||||
230 VAC input | 1 mA max. | |||||
Inrush current * |
115 VAC input | 16 A typ. | ||||
230 VAC input | 32 A typ. | |||||
Output characteristics |
Rated output current | 3.75 A | 5 A | |||
Rated output power | 90 W | 120 W | ||||
Maximum boost current | — | 6 A | ||||
Voltage adjustment range * | 23.0 to 24.1 V | 21.6 to 28 V (with V. ADJ) | ||||
Ripple noise voltage * |
100 to 240 VAC input |
300 mVp-p max. at 20 MHz of bandwidth |
150 mVp-p max. at 20 MHz of bandwidth |
|||
Input variation influence * | 0.5% max. | |||||
Load variation influence * | 1.5% max. | |||||
Temperature variation influence |
100 to 240 VAC input |
0.05%/°C max. | ||||
Start up time * | 115 VAC input | 1000 ms max. | 1000 ms max. | |||
230 VAC input | 1000 ms max. | 1000 ms max. | ||||
Hold time * | 115 VAC input | 25 ms typ. | 35 ms typ. | |||
230 VAC input | 130 ms typ. | 35 ms typ. | ||||
Additional functions |
Overload protection | Yes, automatic reset, intermittent operation type, Refer to Overload Protection on catalog for details. |
||||
Overvoltage protection | Yes, 110% or higher of rated output voltage (90 W), 130% or higher of rated output voltage (120 W), power shut off (shut off the input voltage and turn on the input again, Refer to Overvoltage Protection on catalog for details. |
|||||
Series operation | Yes (For up to two Power Supplies, external diodes are required.) | |||||
Parallel operation | Yes (For up to two Power Supplies), Refer to Parallel Operation on catalog for details. |
|||||
Output indicator | Yes (LED: Green) | |||||
Alarm indicator | Yes (LED: Red) | |||||
Indication monitor |
Measurement and display details |
Refer to Communication and Indication Items on catalog for details. |
||||
Main display | 7-segment LED (White) |
None | 7-segment LED (White) |
None | ||
Ethernet communication |
Measurement and display details |
Refer to Communication and Indication Items on catalog for details. |
||||
Communication protocol |
EtherNet/IP, Modbus TCP | |||||
Physical layer | 100BASE-TX | |||||
Communication specifications |
Refer to Communication Specifications on catalog for details. | |||||
Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals and output terminals, all EtherNet/IP ports), current cutoff 20 mA |
||||
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA |
||||||
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 30 mA |
||||||
0.5 kVAC for 1 min. (between all output terminals and all EtherNet/IP ports), current cutoff 30 mA |
||||||
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
|||||
100 MΩ min. (between all EtherNet/IP ports and all input terminals) at 500 VDC |
||||||
Environment | Ambient operating temperature * | -40 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing) |
||||
Storage temperature | -40 to 85°C (with no condensation or icing) | |||||
Ambient operating humidity | 95% max. (Storage humidity: 95% max.) | |||||
Vibration resistance | 10 to 55 Hz, maximum 5 G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions |
|||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | |||||
Reliability | MTBF * | 110,000 hrs typ. |
150,000 hrs typ. |
110,000 hrs typ. |
140,000 hrs typ. |
|
Life expectancy * | 10 years min. | |||||
Construction | Weight | 350 g max. | 400 g max. | |||
Cooling fan | No | |||||
Degree of protection | IP20 by EN/IEC 60529 |
Power rating | 240 W | 480 W | ||||
---|---|---|---|---|---|---|
Rated output voltage (DC) | 24 V | 24 V | ||||
Indication monitor | Included | None | Included | None | ||
Efficiency * | 115 VAC input | 91% typ. | 91% typ. | 92% typ. | 92% typ. | |
230 VAC input | 93% typ. | 93% typ. | 94% typ. | 94% typ. | ||
Input conditions |
Voltage range * | Single-phase, 85 to 264 VAC, 90 to 350 VDC, 265 to 300 VAC (1 second) |
||||
Frequency * | 50/60 Hz (47 to 63 Hz) | 50/60 Hz (47 to 63 Hz) | ||||
Input current * | 115 VAC input | 2.4 A typ. | 2.4 A typ. | 4.6 A typ. | 4.6 A typ. | |
230 VAC input | 1.2 A typ. | 1.2 A typ. | 2.3 A typ. | 2.3 A typ. | ||
Power factor * | 0.9 min. | |||||
Leakage current * |
115 VAC input | 0.5 mA max. | ||||
230 VAC input | 1 mA max. | |||||
Inrush current * |
115 VAC input | 16 A typ. | ||||
230 VAC input | 32 A typ. | |||||
Output characteristics |
Rated output current | 10 A | 20 A | |||
Rated output power | 240 W | 480 W | ||||
Maximum boost current | 15 A | 30 A | ||||
Voltage adjustment range * | 21.6 to 28 V (with V. ADJ) | |||||
Ripple noise voltage * |
100 to 240 VAC input |
140 mVp-p max. at 20 MHz of bandwidth |
130 mVp-p max. at 20 MHz of bandwidth |
|||
Input variation influence * | 0.5% max. | |||||
Load variation influence * | 1.5% max. | |||||
Temperature variation influence |
100 to 240 VAC input |
0.05%/°C max. | ||||
Start up time * | 115 VAC input | 1000 ms max. | 1000 ms max. | |||
230 VAC input | 1000 ms max. | 1000 ms max. | ||||
Hold time * | 115 VAC input | 35 ms typ. | 25 ms typ. | |||
230 VAC input | 35 ms typ. | 25 ms typ. | ||||
Additional functions |
Overload protection | Yes, automatic reset, intermittent operation type, Refer to Overload Protection on catalog for details. |
||||
Overvoltage protection | Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again), Refer to Overvoltage Protection on catalog for details. |
|||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||||
Parallel operation | Yes (For up to two Power Supplies), Refer to Parallel Operation on catalog for details. |
|||||
Output indicator | Yes (LED: Green) | |||||
Alarm indicator | Yes (LED: Red) | |||||
Indication monitor |
Measurement and display details |
Refer to Communication and Indication Items on catalog for details. |
||||
Main display | 7-segment LED (White) |
None | 7-segment LED (White) |
None | ||
Ethernet communication |
Measurement and display details |
Refer to Communication and Indication Items on catalog for details. |
||||
Communication protocol |
EtherNet/IP, Modbus TCP | |||||
Physical layer | 100BASE-TX | |||||
Communication specifications |
Refer to Communication Specifications on catalog for details. | |||||
Insulation | Withstand voltage | 3.0 kVAC for 1 min. (between all input terminals and output terminals, all EtherNet/IP ports), current cutoff 20 mA |
||||
2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA |
||||||
1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 30 mA |
||||||
0.5 kVAC for 1 min. (between all output terminals and all EtherNet/IP ports), current cutoff 30 mA |
||||||
Insulation resistance | 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC |
|||||
100 MΩ min. (between all EtherNet/IP ports and all input terminals) at 500 VDC |
||||||
Environment | Ambient operating temperature * | -40 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing) |
||||
Storage temperature | -40 to 85°C (with no condensation or icing) | |||||
Ambient operating humidity | 95% max. (Storage humidity: 95% max.) | |||||
Vibration resistance | 10 to 55 Hz, maximum 5 G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions |
|||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | |||||
Reliability | MTBF * | 100,000 hrs typ. |
130,000 hrs typ. |
90,000 hrs typ. |
120,000 hrs typ. |
|
Life expectancy * | 10 years min. | |||||
Construction | Weight | 700 g max. | 1,100 g max. | |||
Cooling fan | No | |||||
Degree of protection | IP20 by EN/IEC 60529 |
* Refer to Definitions of the Terms Under Ratings, Characteristics, and Functions on catalog.
Standards
Standards | Harmonic current emissions |
Conforms to EN 61000-3-2 | |
---|---|---|---|
EMI | Conducted emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | |
Radiated emissions |
Conforms to EN 61204-3 Class B, EN 55011 Class B | ||
EMS | Conforms to EN 61204-3 high severity levels | ||
Safety standards | UL 508 (For 30 W, 60 W, and 90 W only Class 2 Output: Per UL 1310) CSA C22.2 No. 107.1 (For 30 W, 60 W, and 90 W only Class 2 Output: Per CSA C22.2 No. 223) UL 62368-1 (Recognition) OVC II (≤3000 m) Pol2 (For 30 W, 60 W, and 90 W only LPS) CSA C22.2 No. 62368-1 (cUR) OVC II (≤3000 m) Pol2 (For 30 W, 60 W, and 90 W only LPS) EN 62477-1 OVC III (≤2000 m) OVC II (2000 m < and ≤ 3000 m) Pol2 EN 62368-1 OVC II (≤3000 m) Pol2 (For 30 W, 60 W, and 90 W only LPS) RCM (EN61000-6-4) Korea Radio Waves Act (Law No. 10564) Conforms to PELV (EN/IEC 60204-1) Conforms to EN/IEC 61558-2-16 |
||
SEMI | Conforms to F47-0706 (200 to 240 VAC input) |
• EMI (radiated emissions) conform to Class B when this Power Supply is installed in a control panel.
• EN/IEC 61558-2-16
The S8VK-X was designed based on EN/IEC 61558-2-16.
Currently, IEC 61558-2-17 has been replaced by IEC 61558-2-16.
When certification was received for EN/IEC 60204-1 (Machinery Safety), it was necessary to go through a control
transformer to the control circuits. However, a control transformer is not always necessary for product that have been
certified for the safety standard for OVCIII or for product that use a transformer that conforms to EN/IEC 61558-2-16.
• Safety Standards for a DC Input
When DC is used, UL 62368-1, cUR (CSA C22.2 No. 62368-1), EN/IEC 62368-1, EN 62477-1 and EN/IEC 61558-2-16
are applicable to safety standards.
Safety standard compliance is achievable by connecting a UL-certified fuse as specified below.
Select an external fuse that satisfies the following conditions:
S8VK-X03005-EIP, S8VK-X06012-EIP, S8VK-X06024-EIP (350 VDC or more, 6 A)
S8VK-X09024[]-EIP, S8VK-X12024[]-EIP, S8VK-X24024[]-EIP (350 VDC or more, 8 A)
S8VK-X48024[]-EIP (350 VDC or more, 12 A)
• To comply with PELV output requirements for EN/IEC 60204-1, ground the negative side of the output (-V) to a protective
earth (PE).
Definitions of the Terms Under Ratings, Characteristics, and Functions
conditions |
Efficiency | The value is when both rated output voltage and rated output current are satisfied. |
---|---|---|
Voltage range | Do not use an inverter output for the product. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the product may result in smoking or burning. If the input is connected to a UPS, do not connect a UPS with a square-wave output. Doing so will cause the internal temperature of the product to increase, possibly causing smoking or burning. |
|
Frequency | ||
Input current | The value is when both rated output voltage and rated output current are satisfied. |
|
Power factor | The value is when both rated output voltage and rated output current are satisfied. |
|
Leakage current |
The value is determined according to the Electrical Appliances and Material Safety Act. |
|
Inrush current | Values for a cold start at 25°C. Refer to Inrush Current, Startup Time, and Output Hold Time on catalog for details. |
|
Output characteristics |
Voltage adjustment range |
If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than of the voltage adjustment range. When adjusting the output voltage, confirm the actual output voltage from the product and be sure that the load is not damaged. |
Ripple noise voltage |
The value is when both rated output voltage and rated output current are satisfied. A characteristic when the ambient operating temperature is 25°C. |
|
Static input variation influence |
This is the maximum variation in the output voltage when the input voltage is gradually changed within the allowable input voltage range at the rated output voltage and rated output current. |
|
Load variation influence |
100 to 240 VAC input, in the range of 0 A to the rated output current. | |
Startup time | The value is when both rated output voltage and rated output current are satisfied and at room temperature (25°C). Refer to Inrush Current, Startup Time, and Output Hold Time on catalog for details. |
|
Hold time | The value is when both rated output voltage and rated output current are satisfied and at room temperature (25°C). Refer to Inrush Current, Startup Time, and Output Hold Time on catalog for details. |
|
Environment | Ambient operating temperature |
At -40 to -25°C, time will be required before the rated output voltage is output after the input voltage is input. Also, the ripple noise value may exceed the value shown in the above table. |
Reliability | MTBF | MTBF is calculated according to JEITA RCR-9102. MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates reliability of devices. Therefore, it does not necessarily represent a life of the product. |
Life expectancy |
Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on catalog for details |
Communication and Indication Items
Item | Communication * | Indication monitor * |
Resolution | Data update cycle |
Details | |
---|---|---|---|---|---|---|
Output voltage measurement |
Yes | Yes | 0.1 V | 5 ms | Measurement accuracy ±2% (percentage of output voltage value) ±1 digit |
|
Output current measurement |
Yes | Yes | 0.1 A | 5 ms | Measurement accuracy ±5% (percentage of rated output current) ±1 digit |
|
Peak hold current measurement | Yes | Yes | 0.1 A | 5 ms | Measurement accuracy ±5% (percentage of rated output current) ±1 digit |
|
Years until replacement |
Yes | Yes | 0.1 years | 1 min | Range 0.0 to 15.0 years (communication) FUL (Full) / HLF (Half) / 0.0 to 4.9 years (indication monitor) |
|
Percentage until replacement |
Yes | Yes | 0.1% | 1 min | Range 0.0 to 100% |
|
Total run time | Yes | Yes | Communication | 1 h | 1 min | Range 0 to 262,800 h (communication) 0 to 263 kh (indication monitor) |
Indication monitor |
1 kh | |||||
Continuous run time |
Yes | None | 1 min | 1 min | Range 0 to 15,768,000 min |
|
Self-diagnostics | Yes | Yes | None | None | Refer to Self-Diagnostics Function on catalog for details. |
|
Product model | Yes | None | None | None | Product model is expressed in ASCII code |
|
Serial number | Yes | None | None | None | Expressed in hexadecimal (4-byte) |
|
Firmware version | Yes | None | None | None | Expressed in hexadecimal (2-byte) |
|
MAC address | Yes | None | None | None | None | |
IP address | Yes | None | None | None | None | |
IP address setting method |
Yes | None | None | None | Static IP address/BOOTP selection |
Note: For details on the communication function and setting method, refer to the Switch Mode Power Supply S8VK-X
Communication Manual (Man. No. T213).
* Communication cycle can be set from 100 to 10,000 ms. The indication update cycle is 50 ms.
Inrush Current, Startup Time, and Output Hold Time
Note: Twice the normal inrush current will flow during parallel operation or for backup operation. Also, if crossover wiring
is used for N number of Power Supplies, an inrush current of N times the inrush current for a standalone Power Supply
will flow. Therefore, check the fusing characteristics of fuses and operating characteristics of breakers making sure that
the external fuses will not burn out and the circuit breakers will not be activated by the inrush current.
Overload Protection
When the load current reaches 121% to 160% of the rated current for S8VK-X03005-EIP, S8VK-X06012-EIP, S8VK-X06024-EIP, and S8VK-X12024[]-EIP, 101% to 110% for S8VK-X09024[]-EIP, or 151% to 165% for S8VK-X24024[]-EIP and S8VK-X48024[]-EIP, output voltage is automatically lowered to protect the Power Supply from short-circuit currents and overcurrents.
When the output current falls within the rated range, the overload protection function is automatically cleared.
Note: 1. Internal parts may possibly deteriorate or be damaged if a short-circuited or overcurrent state continues during
operation.
2. Internal parts may possibly deteriorate or be damaged if the Power Supply is used for applications with frequent
inrush current or overloading at the load end. Do not use the Power Supply for such applications.
Overvoltage Protection
Overvoltage will be detected to prevent the load from being subjected to excessive voltage when the feedback circuit in the Power Supply fails, etc.
If an excessive voltage that is approximately 130% of the rated output voltage (but approximately 110% of the rated output voltage for only the S8VK-X09024[]-EIP) or more is output, the output voltage is shut OFF.
Reset the input power by turning it OFF for at least three minutes and then turning it back ON again.
Note: Do not turn ON the power again until the cause of the overvoltage has been removed.
Communication Specifications
Item | Specification | |
---|---|---|
Media access method | CSMA/CD | |
Modulation system | Baseband | |
Topology | Star configuration | |
Transmission speed | 100 Mbps | |
Transmission medium | Twisted pair cable (with shield: STP): Category 5, 5e or above | |
Maximum transmission distance (distance between hub and node) |
100 m | |
Tag data Link |
Class1 | Connection resource: 1 max. |
Number of connected nodes | 1 | |
Number of tag sets | 1 | |
Packet interval (RPI) | 100 to 10,000 ms | |
Time-out value | Multiple of RPI | |
Connection type | Point To Point Connection (fixed) | |
Explicit Message |
Class3 | Number of clients that can communicate at one time: 2 max. |
UCMM | Number of clients that can communicate at one time: 2 max. | |
Modbus message |
Modbus TCP | Number of clients that can communicate at one time: 2 max. |
Factory default values |
IP address | 192.168.250.20 |
Subnet mask | 255.255.255.0 | |
Default gateway | 0.0.0.0 | |
IP address setting method | Static IP address |
Module Status and Network Status Indicators
Name | Color | Status | Operating status |
---|---|---|---|
Module status Indicator (MS) |
Green | Lit | Normal |
Flashing | — | ||
Red | Lit | RAM abnormality, EEPROM abnormality | |
Flashing | Voltage measurement abnormality, current measurement abnormality |
||
– | Not lit | No power supply | |
Green/Red | Flashing | When power is turned ON | |
Network status Indicator (NS) |
Green | Lit | Connection established |
Flashing | Connection not established | ||
Red | Lit | Multiple IP addresses | |
Flashing | Connection timeout BOOTP server connection abnormality |
||
— | Not lit | No power supply | |
Green/Red | Flashing | When power is turned ON |
Communication Reset Function
This function temporarily resets the communication settings to their factory default values. Use this function when the IP address previously set is no longer known and communication is not possible.
Setting Method
(1) With the reset key pressed, turn on the power supply.
(2) Continue to hold the reset key for 10 seconds.
While pressed, an alarm indicator will flash in 0.5-second intervals.
(For models with an indication monitor, the main display and operation indicator will also repeatedly turn all indicators
on and off in 0.5-second intervals.)
(3) After 10 seconds have elapsed, the system shifts into the communication reset state, and the communication setting
values temporarily reset to their factory default values.
In the communication reset state, the alarm indicator will flash in 1-second intervals. (For models with an indication
monitor, the main display and operation indicator will return to normal operation.)
(4) In the communication reset state, reset the communication settings from the host device.
(5) After setting, turn on the power supply once again, and confirm that the set values have been changed.
Note: 1. After confirming that the product output indicator has turned off, turn on the power supply once again.
2. The only way to exit the communication reset state is to restart the power supply.
3. If you do not change the communication settings during step (4), settings will return to their prior values once
the communication reset is ended.
Switching Indications
All indicators of the indication monitor will be lit for 1 second when power is turned on. After that, each status can be displayed using the Indication switching key.
Peak Hold Current
The output current maximum value is stored as the peak hold current. (5 ms average value)
Measurement is not performed for approximately 3 seconds immediately after the input power is turned ON.
Peak Hold Curmrent Reset
When the peak hold current is displayed, it can be reset by pressing the Reset key for 3 seconds or more.
Note: For types without an indication monitor, it is not possible to reset the peak hold current via reset key operation.
Replacement Time Calculation Function
This Power Supply is equipped with electrolytic capacitors. The electrolyte inside the electrolytic capacitors penetrates the sealing rubber and evaporates as time passes after it is manufactured. This causes deterioration of characteristics, such as decreasing the capacitance. Due to this deterioration of the characteristics of the electrolytic capacitor, this Power Supply decreases its performance as time passes. The replacement time calculation function calculates an approximate period left for maintenance of this Power Supply due to deterioration of electrolytic capacitors. Use this function to know the approximate replacement time of the Power Supply.
Note: The replacement time calculation function indicates an approximate period left for maintenance, based on deterioration
of the electrolytic capacitors. It does not predict failures resulting from other causes.
Principle of Operation
The deterioration speed of the electrolytic capacitors varies considerably with the ambient temperature. (Generally the speed follows the Arrhenius Law, i.e., for every 10°C increase in the temperature, the rate of degradation doubles.) The S8VK-X monitors the temperature inside the Power Supply, and calculates the amount of deterioration according to the running hours and internal temperature.
Note: 1. Due to degradation of internal electronic parts, replace the Power Supply approximately 15 years after purchase
even if the replacement time calculation for years and percentage do not appear.
2. The replacement time is accelerated or decelerated according to operating conditions. Periodically check
indication.
3. The accuracy of the replacement time calculation function will be reduced in applications where the input power
turns ON and OFF frequently.
Years until replacement
(Indication monitor)
is indicated at the time of purchase (when initially powered on), and continues to be indicated for approximately one month.
Afterward, the state of deterioration for the electrolytic capacitor is calculated based on the usage environment, and is indicated when deterioration progresses. When the years until replacement reaches 5 years or less, it is indicated in 0.1 step increments within the range of 4.9 to 0.0. (Depending on the usage environment, the number of years may be indicated after without being indicated.)
(Communication)
Communication is calculated in 0.1 step increments within a range of 15.0 to 0.0.
Note: The number of years until replacement may vary if there are frequent load variations or in locations where the ambient
temperature fluctuates drastically.
Percentage until replacement
With the number of years until replacement at the time of manufacture set as 100%, as deterioration of the electrolytic capacitor progresses through use, it decreases in 0.1% step increments.
Difference between Expected Life and Replacement Time
OMRON calculates the expected life based on the following conditions.
1.Rated input voltage
2. Load rate: 50%
3. Ambient temperature: +40°C
4. Standard mounting
Note: As the values were calculated using an aluminum electrolytic condenser temperature rise test, they are not
guaranteed. Use this data as a reference for maintenance and replacement time calculation.
The expected life span of the S8VK-X is 10 years minimum.
Also, a replacement time calculation function is included among the functions of the S8VK-X. The replacement time is the service life (the Power Supply’s internal temperature is monitored at all times) of the internal electrolytic capacitor in actual operating conditions, and varies according to the customers operating conditions. 15 years is taken as the maximum period of the maintenance forecast.
Total Run Time
The accumulated value of the product’s time powered on is measured as the total run time.
(With indication monitor)
Total run time increases in (kh) steps with use.
(Communication)
Total run time increases in (h) steps with use.
Time Chart
Note: 1. The total run time does not include the time that the Power Supply is OFF.
2. The total run time measures the total time that power is being supplied and is not related in any way to deterioration
in the electrolytic capacitor built into the Power Supply or to the effects of the ambient temperature.
Continuous Run Time (Communication Only)
The product’s time powered on is measured as continuous run time, and the continuous run time increases in 1 (min) steps with use.
Continuous run time will be reset when power is turned off.
Time Chart
Note: 1. The continuous run time does not include the time that the Power Supply is OFF.
2. The continuous run time measures the total time that power is being supplied and is not related in any way to
deterioration in the electrolytic capacitor built into the Power Supply or to the effects of the ambient temperature.
Model | S8VK-X06024-EIP, S8VK-X09024-EIP, S8VK-X12024-EIP, S8VK-X24024-EIP, S8VK-X48024-EIP |
---|
Weight | N/A |
---|---|
Model | S8VK-X06024-EIP, S8VK-X09024-EIP, S8VK-X12024-EIP, S8VK-X24024-EIP, S8VK-X48024-EIP |
Model | S8VK-X06024-EIP, S8VK-X09024-EIP, S8VK-X12024-EIP, S8VK-X24024-EIP, S8VK-X48024-EIP |
Related products
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details