Contact Us:
sales@inosaki.com

Domestic TeSys Deca GV2 – GV2PM – Thermal Magnetic Motor Circuit Breakers – Schneider Circuit Breakers

$ 32.20$ 34.04

Specifications

main information
Part Number GV2PM08C GV2PM14C
Product Series TeSys Deca TeSys Deca
product name TeSys GV2 TeSys GV2
product short name GV2PM GV2PM
product type Breaker Breaker
Applications Motor protection Motor protection
number of poles 3P 3P
Additional information
Grid type AC AC
Network frequency 50/60 Hz conforming to IEC 60947-2 50/60 Hz conforming to IEC 60947-2
control type Knob Knob
installation method Rail installation Rail installation
installation location Vertical horizontal vertical
horizontal direction
Motor power (kW) 0.75 kW at 230 V AC 50/60 Hz 2.2 kW at 230 V AC 50/60 Hz
1.5 kW at 400 V 4 kW at 400 V
1.5 kW at 415 V 4 kW at 415 V
1.5 kW at 440 V AC 50/60 Hz 4 kW at 440 V AC 50/60 Hz
Rated current [In] 4A 10A
Trip unit type Thermomagnetic Thermomagnetic
Electromagnetic trip current 51A 138A
Thermal overload protection setting range 2.5…4A 6…10A
isolation function Applies to IEC 60947-1 § 7-1-6 Applies to IEC 60947-1 § 7-1-6
Mechanical shock resistance 0.5 J IK04 0.5 J IK04
phase loss sensitivity Is compliant with IEC 60947-4-1 § 7-2-1-5-2 Is compliant with IEC 60947-4-1 § 7-2-1-5-2
use category Type AC conforms to IEC 60947-2 Type AC conforms to IEC 60947-2
AC-3 conforms to IEC 60947-4-1 AC-3 conforms to IEC 60947-4-1
Rated working voltage [Ue] 690 V AC 50/60 Hz conforming to IEC 60947-2 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage [Ui] 690 V AC 50/60 Hz conforming to IEC 60947-2 690 V AC 50/60 Hz conforming to IEC 60947-2
600 V AC 50/60 Hz conforming to UL 508 600 V AC 50/60 Hz conforming to UL 508
600 V AC 50/60 Hz conforming to CSA C22.2 No 14 600 V AC 50/60 Hz conforming to CSA C22.2 No 14
Conventional thermal current [Ith] 4 A conforming to IEC 60947-4-1 9 A conforming to IEC 60947-4-1
Rated impulse withstand voltage [Uimp] 6 kV according to IEC 947-2 6 kV according to IEC 947-2
power consumption per pole 2.5W 2.5W
Mechanical life 100000 times 100000 times
Electrical life 100000 cycles for AC-3 at 440 V In 100000 cycles for AC-3 at 440 V In
100000 cycles for AC-3 at 440 V In/2 100000 cycles for AC-3 at 440 V In/2
maximum conversions 25 cyc/h 25 cyc/h
specified load Continuous according to IEC 60947-4-1 Continuous according to IEC 60947-4-1
Wiring capacity Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit: Power circuit: Screw-in terminals 2 1…6 mm² Cable option: Solid without wire terminals Power circuit:
Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals Screw-in terminals 2 1.5…6 mm² Cable option: Flexible without wire terminals
Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with wire terminals Power circuit: Screw-in terminals 2 1…4 mm² Cable selection: Flexible with wire terminals
Tightening torque 1.7 Nm via screw-in terminal cable 1…4 mm² 1.7 Nm via screw-in terminal cable 1…4 mm²
1.7 Nm via screw-in terminal cable 1…6 mm² 1.7 Nm via screw-in terminal cable 1…6 mm²
1.7 Nm via screw-in terminal cable 1.5…6 mm² 1.7 Nm via screw-in terminal cable 1.5…6 mm²
Breaking capacity Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Icu: >= 100 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 Icu: 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Icu: >= 100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 Icu: 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Icu: 3 kA at 690 V AC 50/ 60 Hz conforming to IEC 60947-2 Icu: 3 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operating short-circuit breaking capacity [Ics] 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 2
high 89mm 89 mm
width 44.5 mm 44.5 mm
depth 91 mm 91 mm
product weight 0.26kg 0.26kg
environment
Standards compliant GB 14048.4 GB 14048.4
IEC 60947-1 IEC 60947-1
IEC 60947-2 IEC 60947-2
IEC 60947-4-1 IEC 60947-4-1
certified product CCC CCC
UKCA UKCA
CE CE
Protective measures TH TH
IP protection class IP20 complies with screwed (body) IP20 complies with screwed (body)
Shock and vibration resistance Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27 Shock resistance 11 ms (30 gn) conforming to IEC 60068-2-27
Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6 Shock resistance (5 gn (5…150 Hz)) conforming to IEC 60068-2-6
ambient temperature -20…40 °C In cabinet -20…40 °C In cabinet
-20…60 °C Body -20…60 °C Body
storage environment temperature -40…80°C -40…80°C
Fire resistance and abnormal high temperature resistance 960 °C conforming to IEC 60695-2-1 960 °C conforming to IEC 60695-2-1
working altitude <= 2000m <= 2000m
packaging unit
Unit Type of Package 1 PCE PCE
Number of Units in Package 1 1 1
Package 1 Height 4.93cm 5.14cm
Package 1 Width 9.02 cm 9.29cm
Package 1 Length 9.38cm 9.78cm
Package 1 Weight 282.6g 299.2g
Unit Type of Package 2 S02 S02
Number of Units in Package 2 20 20
Package 2 Height 15.0cm 15.0cm
Package 2 Width 30.0cm 30.0cm
Package 2 Length 40.0cm 40.0cm
Package 2 Weight 6.044 kg 6.376 kg
Unit Type of Package 3 P06 P06
Number of Units in Package 3 400 400
Package 3 Height 90.0cm 90.0cm
Package 3 Width 60.0cm 60.0cm
Package 3 Length 80.0cm 80.0cm
Package 3 Weight 130.88kg 137.52kg
contract warranty
Warranty 18 months 18 months

Additional information

Weight N/A
Dimensions N/A
Amp, A

,

Related Products

SICK_sensor_Photoelectric_sensor_W12-2 Laser_WL12G-3B2531S37
IDS Camera_uEye_CP_Rev2
$ 763.37 - $ 822.71
SCHNEIDER_TeSys Electronic Overcurrent Relay,220 V AC,Setting Range,1.2..
c-mount_lens_6mm_tamron_6megapixel_ids_ueye-3
Ricoh_Lens_AE00150
M4
Select your currency